Vav/zone controller programming, Vav/zone confi guration screens, Vcm-x / rne operator interface sd 66 – Orion System VCM-X/RNE Controller User Manual
Page 66: Vav zone confi guration

VAV/ZONE CONTROLLER PROGRAMMING
VCM-X / RNE Operator Interface SD
66
VAV/Zone Confi guration Screens
VAV Zone Confi guration
In order to correctly set up the VAV/Zone Controller, you must fi rst
confi gure several parameters in regard to the type of system and operat-
ing parameters for the VAV/Zone Controller you have installed. Most
of these values and operating parameters are only set once at the initial
system setup and are never changed.
Modular Service Tool Instructions
From any Menu Screen, press the
button. The
Unit Selection Screen, shown below, will appear requesting that you
enter the unit ID number.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
*00*
Enter the correct unit ID number of the VAV/Zone controller you want
to confi gure, and press
. You must type in the number, even
if it is “1”. Once communication is established, the *00* at the bottom
will disappear. Then
press
<
>
. You will then see Unit Confi guration
Screen #1. Press
to save entered data and
press
<
>
to
scroll through the screens.
NOTE:
If the *00* remains, it indicates a communication failure
to the controller.
System Manager SD Instructions
From any Main screen, press
. The screen below will
appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will be
displayed.
Unit Selection *00*
Enter Unit ID#
Selected ID#: XXXX
Enter the Unit ID of the controller you wish to change schedules for
and press
. You must type in the number, even if it is “1”.
Once communication is established, the *00* at the top will disappear.
Then
press
<
>
.
NOTE:
If the *00* remains, it indicates a communication
failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll down to the ‘Confi gure Unit’ option and press
. This
will take you to the fi rst Confi guration Screen shown below.
Confi guration Screen #1 - Box Confi guration
XX Box Cnfg IDXXXX
Box Configuration
COOLING ONLY BOX
Use < Or > To Change
This Box Control Code will operate in one of four possible modes. The
box designation will display on the top line of all screens. Select one
of the following options:
0 = COOLING ONLY BOX (will display as CO Box)
1 = H/C CHANGEOVER BOX (will display as HC Box)
2 = SERIES FAN BOX (will display as SF Box)
3 = PARALLEL FAN BOX (will display as PF Box)
Confi guration Screen #2 - Damper Operation
XX Box Cnfg IDXXXX
Damper Operating
Mode: DIRECT ACTING
Use < Or > To Change
Select Direct Acting or Reverse Acting. If the damper opens in a
clockwise direction, it is DIRECT ACTING. If the damper opens in a
counter-clockwise direction, it is REVERSE ACTING.
CAUTION: If you change this setting, you MUST cycle
power to the controller to allow it to re-calibrate
the damper feedback positions for its new
direction of control!