beautypg.com

Vav/zone controller programming, Vav/zone confi guration screens, Vcm-x / rne operator interface sd 66 – Orion System VCM-X/RNE Controller User Manual

Page 66: Vav zone confi guration

background image

VAV/ZONE CONTROLLER PROGRAMMING

VCM-X / RNE Operator Interface SD

66

VAV/Zone Confi guration Screens

VAV Zone Confi guration

In order to correctly set up the VAV/Zone Controller, you must fi rst
confi gure several parameters in regard to the type of system and operat-
ing parameters for the VAV/Zone Controller you have installed. Most
of these values and operating parameters are only set once at the initial
system setup and are never changed.

Modular Service Tool Instructions

From any Menu Screen, press the

button. The

Unit Selection Screen, shown below, will appear requesting that you
enter the unit ID number.

Unit Selection
Enter Unit ID#

Selected ID#: XXXX

*00*

Enter the correct unit ID number of the VAV/Zone controller you want
to confi gure, and press

. You must type in the number, even

if it is “1”. Once communication is established, the *00* at the bottom
will disappear. Then

press

<

>

. You will then see Unit Confi guration

Screen #1. Press

to save entered data and

press

<

>

to

scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

System Manager SD Instructions

From any Main screen, press

. The screen below will

appear because this option requires passcode clearance. Only a Level 2
passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will be
displayed.

Unit Selection *00*

Enter Unit ID#

Selected ID#: XXXX

Enter the Unit ID of the controller you wish to change schedules for
and press

. You must type in the number, even if it is “1”.

Once communication is established, the *00* at the top will disappear.
Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication
failure to the controller.

The following screen will be displayed:

Change Setpoints

Configure Unit

Save/Copy/Restore

Scroll down to the ‘Confi gure Unit’ option and press

. This

will take you to the fi rst Confi guration Screen shown below.

Confi guration Screen #1 - Box Confi guration

XX Box Cnfg IDXXXX

Box Configuration

COOLING ONLY BOX

Use < Or > To Change

This Box Control Code will operate in one of four possible modes. The
box designation will display on the top line of all screens. Select one
of the following options:

0 = COOLING ONLY BOX (will display as CO Box)

1 = H/C CHANGEOVER BOX (will display as HC Box)

2 = SERIES FAN BOX (will display as SF Box)

3 = PARALLEL FAN BOX (will display as PF Box)

Confi guration Screen #2 - Damper Operation

XX Box Cnfg IDXXXX

Damper Operating

Mode: DIRECT ACTING

Use < Or > To Change

Select Direct Acting or Reverse Acting. If the damper opens in a
clockwise direction, it is DIRECT ACTING. If the damper opens in a
counter-clockwise direction, it is REVERSE ACTING.

CAUTION: If you change this setting, you MUST cycle

power to the controller to allow it to re-calibrate

the damper feedback positions for its new

direction of control!