Vav/zone controller programming, Vav/zone confi guration screens – Orion System VCM-X/RNE Controller User Manual
Page 68

VAV/ZONE CONTROLLER PROGRAMMING
VCM-X / RNE Operator Interface SD
68
VAV/Zone Confi guration Screens
Confi guration Screen #10 - Dump Zone
XX Box Cnfg IDXXXX
Is This A Dump Zone
(No Actuator): NO
Use < Or > To Change
A “Dump Zone” is used when you want to control a duct heater or
baseboard heater independently. A VAV/Zone Controller board with a
relay expansion board is used for this purpose. No damper or actuator
is used. If you need to control an auxiliary heater, select YES; otherwise,
select NO.
Confi guration Screen #11 - HVAC Unit is on
Separate Loop
XX Box Cnfg IDXXXX
HVAC Unit is on
Separate Loop: NO
Use < Or > To Change
If this system has 1 HVAC unit controlling boxes on multiple loops
and the HVAC unit is on a different loop than this box, select YES;
otherwise, select NO.