Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 58 – Orion System VCM-X/RNE Controller User Manual
Page 58

VCM-X / RNE STATUS
VCM-X / RNE Operator Interface SD
58
VCM-X / RNE Status Screens
Status Screen 7 / RNE - Leaving Water
Temperature 2
RNE v1.00
Leaving Water 2
Temp A: 0.0ºF
Temp B: 0.0ºF
Line 2
Leaving Water Temperature 2
If using the RNE Controller and a second Water Source
Heat Pump Module has been installed and confi gured, this
screen will display Water Temperatures. If not, this screen
will
display
0°F.
Line 3
Leaving Water Temperature A
This line will display the Leaving Water Temperature of
the
fi rst Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the fi rst sensor on the Module
with
address
2.
Line 4
Leaving Water Temperature B
This line will display the Leaving Water Temperature of
the second Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the second sensor on the
Module with address 2.
Status Screen 8 - Coil Temp & Setpoint
VCM-X / RNE v1.00
Coil Tmp...: XX.XºF
Coil Tmp Spt: XX.XºF
Line 2 Coil Temperature or Lowest Coil
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
If this unit has multiple digital scroll compressors and has a
Full Digital Module or Dual Digital Module installed, this
line will display Lowest Coil and will display the lowest of
the multiple suction temperatures. The coil temperatures of
all the coils will be displayed on Status Screens 19 & 20.
Line 3 Coil Temperature Setpoint
During
dehumidifi cation, the Coil Suction Temperature
Setpoint is automatically reset based on the current space
humidity conditions. This is the current calculated Coil
Temperature Setpoint based on that reset.
Status Screen 9 - Outdoor Air Temperature &
Outdoor Air Relative Humidity
VCM-X / RNE v1.00
Outdoor Tmp: XX.XºF
Outdoor RH.: XX.X%
Line 2 Current Outdoor Air Temperature
If an Outdoor Air Temperature Sensor has been installed
and
confi gured on the unit or if an Outdoor Air Broadcast
has
been
confi gured on another Unit Controller on the
system, the Outdoor Air Temperature will appear on
this line. If not, this line will display a temperature that is
half way between the Cooling and Heating Lockout
Setpoints.
Line 3 Current Outdoor Air Relative Humidity
If an Outdoor Humidity Sensor has been installed and
confi gured on the Unit Controller, the Outdoor Air
Relative Humidity Percentage will appear on this line. If
not, this line will display 0%.
Status Screen 10 - OA Dewpoint & Dewpoint
Temp
VCM-X / RNE v1.00
OA Dewpoint.: XX.XºF
Dewpoint Spt: XX.XºF
Line 2 Current Calculated Outdoor Air Dewpoint
Temperature
If both an Outdoor Humidity Sensor and an Outdoor Air
Temperature Sensor have been installed and confi gured on
the unit, the calculated Outdoor Air Dewpoint Temperature
will appear on this line. If not, this screen displays 0°F.
Line 3 Current Outdoor Air Dewpoint Setpoint
The user adjustable Outdoor Air Dewpoint Temperature
Setpoint will appear on this line.