Rne configuration, Rne confi guration screens – Orion System VCM-X/RNE Controller User Manual
Page 41

VCM-X / RNE Operator Interface SD
RNE CONFIGURATION
41
Confi guration Screen #41 - Emergency
Shutdown Input
RNE Cnfg ID 101
Emergency Shutdown
Input: NO
Use < Or > To Change
Select YES if a Smoke Detector/Firestat or other Emergency Shutdown
input is connected to the binary input. If the Emergency Shutdown input
is active, the Supply Fan, Heating and Cooling Relay Outputs will be
disabled. Default is NO.
Confi guration Screen #42 - Return Air Bypass
Control
RNE Cnfg ID 101
Return Air Bypass
Control: NO
Use < Or > To Change
Select YES if your HVAC unit requires Return Air Bypass Control for
Dehumidifi cation Reheat. Default is NO.
Confi guration Screen #43 - Broadcast OA Temp
RNE Cnfg ID 101
Broadcast Outdoor
Temperature: NO
Use < Or > To Change
The RNE can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in
order for this feature to operate. Select YES to Broadcast the Outdoor
Temperature. Default is NO.
Confi guration Screen #44 - Broadcast OA Humidity
RNE Cnfg ID 101
Broadcast Outdoor
Humidity: NO
Use < Or > To Change
The RNE can broadcast its Outdoor Air Humidity reading to other HVAC
units if they are not equipped with their own Outdoor Air Humidity
sensors. A network communications device is required in order for
this feature to operate. Select YES to Broadcast the Outdoor Humidity.
Default is NO.
Confi guration Screen #45 - Broadcast Supply
Temperature
RNE Cnfg ID 101
Broadcast Supply
Temperature: YES
Use < Or > To Change
This broadcast sends the RNE’s Supply Air Temperature to all Control-
lers on its local loop. This broadcast needs to be confi gured on a VAV
or Zoning System using the RNE with Orion VAV/Zone Controllers. A
network communications device is required in order for this feature to
operate. Select YES to Broadcast the Supply Air Temperature. Default
is YES.
Confi guration Screen #46 - Broadcast Status
Fan & Heat
RNE Cnfg ID 101
Broadcast Status
Fan & Heat: NO
Use < Or > To Change
This broadcast sends the RNE’s Supply Fan and Heating Status to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate. Select YES to Broadcast the Fan & Heat Status. Default is NO.
Confi guration Screen #47 - Broadcast Internal
Time Clock
RNE Cnfg ID 101
Broadcast Internal
Time Clock: NO
Use < Or > To Change
This broadcast sends the time from the RNE’s Internal Time Clock to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate, but can also be used to synchronize all Controllers on the local
loop. Select YES to Broadcast the Internal Time Clock. Default is NO.
RNE Confi guration Screens