VAV/ZONE CONTROLLER PROGRAMMING

VCM-X / RNE Operator Interface SD

72

VAV/Zone Setpoint Screens

Setpoint Screen #13 - Zone Alarm Delay

XX Box Spts IDXXXX

Zone Alarm Delay

Must Be Out Of

Limits For.: XXX Min

As mentioned above, if you confi gure the controller to generate zone
temperature alarms, this is the amount of time after the box goes into the
Occupied Mode that the temperature must be outside the alarm limits
before an alarm is generated.

Description

Minimum

Default

Maximum

Out of Limits

1 Min

30 Min

300 Min

Setpoint Screen #14 - Day/Night Schedule

XX Box Spts IDXXXX

Day/Night Schedule

Control #: X

0=AHU 1-5=Scheduler

This screen allows you to set the VAV/Zone Controller to operate on a
remote schedule instead of the schedule that is contained in the VCM-X
or RNE Controller. Enter

<0>

to operate on the AHU schedule. Enter

<1-

5>

to use an external schedule. A GPC Plus is required for schedules 1-5.

Description

Minimum

Default

Maximum

Schedule Control Number

0

0

1 to 5

Setpoint Screen #15 - Maximum Slide Offset

XX Box Spts IDXXXX

Maximum Slide Offset

Effect on Spt.: XºF

If the Flush Mount Wall Sensor has the optional Setpoint Slide Adjust,
this is the maximum amount you can adjust the heating and cooling
setpoints up or down as the slide is moved from the center position to
its full up or down position.

Description

Minimum

Default

Maximum

Effect on SP

0ºF

0ºF

6ºF

Setpoint Screen #16 - Push-Button Override

Duration

XX Box Spts IDXXXX

Push-Button Override
Duration : X.X Hr

If the Flush Mount Wall Sensor has the optional Push-Button Over-
ride, this is the amount of the VAV/Zone Controller will resume using
its Occupied Setpoints during unoccupied mode. This will generate a
call for the Air Handler to start its fan and provide heating or cooling,
depending on how you confi gure the Air Handler.

Description

Minimum

Default

Maximum

Duration

0.0 Hr

0.0 Hr

8.0 Hr

Setpoint Screen #17 - Maximum EMS Offset

XX Box Spts IDXXXX

Maximum EMS Setpoint

Offset...: XXºF

If the Energy Management System (EMS) is activated, the heat and cool
setpoints can be spread apart by this amount.

Description

Minimum

Default

Maximum

Maximum EMS Setpoint

Offset

0ºF

0ºF

30ºF

Setpoint Screen #18 - Sensor Calibration for

Space Temp and Supply Air Temp

Sensor Calibration

SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº

[SAT Only if Sensor]

The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease
a reading.

NOTE: The Supply Air Temperature calibration offset only oper-

ates on the reading when the VAV/Zone Controller has
its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from
a global broadcast, you will need to go to the air handler
to calibrate the temperature reading.

Description

Minimum

Default

Maximum

SPC (Space Temp)

-100ºF

0ºF

+100ºF

SAT (Supply Air)

-100ºF

0ºF

+100ºF