Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 60 – Orion System VCM-X/RNE Controller User Manual

Page 60

background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

60

Status Screen 16 - Supply Air & Return Air

CFM

VCM-X / RNE v1.00
SA CFM: 0.00 K

RA CFM: 0.00 K

[Optional Inputs]

Line 2 Supply Air CFM

If a supply air airfl ow monitoring station is being used, this

is the current CFM reading of that device.

K = 1000

Line 3 Return Air CFM

If a return air airfl ow monitoring station is being used, this

is the current CFM reading of that device. K = 1000

Line 4 Indicates That These are Optional Inputs

These inputs may or may not have live data to display.

Status Screen 17 - Building Pressure & Output %

VCM-X / RNE v1.00

Building Pr..: X.XX”
Press Output: XXX%

[ Optional Outputs ]

Line 2 Current Building Pressure

Indicates the current Building Pressure. This display

requires the installation of a Building Pressure Sensor.

If you don’t have a Building Pressure Sensor correctly

installed and wired to the controller, this line will display

“0.0”.

Line 3 Current Building Pressure Output Signal Percentage

Indicates the output signal percentage being supplied

to the Exhaust Fan VFD controller or Exhaust Damper

Actuator when you have confi gured one of these options

for your HVAC unit.

If you have not confi gured Building Pressure Control,

this line will display [No Press Out Confg].

Line 4 Indicates That These Are Optional Outputs

This output may or may not have live data to display.

Status Screen 18 - MODGAS Output %

& MHGRV Output %

VCM-X / RNE v1.00

MODGAS Pos..: XXX%
MHGRV Pos...: XXX%
[Optional Equipment]

VCM-X / RNE Status Screens

Line 2 Current MODGAS Heating Output Signal

Indicates the percentage of the output signal being supplied
to the MODGAS Controller when you have one
connected to your HVAC unit. If you do not have a
MODGAS controller connected to your

Unit Controller

,

this screen will indicate [MODGAS NOT CONNECTED].

Line 3 Current MHGRV Reheat Valve Output Signal
Percentage

Indicates the percentage of the output signal being supplied

to the MHGRV controller when you have one connected

to

your

Unit Controller

.

If you do not have an

MHGRV controller connected to your Unit Controller,

this screen will indicate [MHGRV NOT CONNECTED].

Line 4 Optional Equipment

Indicates that these outputs are optional and therefore may

or may not have live data to display.

Status Screen 19 - Mod Heating & Cooling %

VCM-X / RNE v1.00

Mod Cooling: XXX%
Mod Heating: XXX%

[ Optional Outputs ]

Line 2 Current Modulating Cooling Output Signal Percentage

Indicates the percentage of the output signal being supplied

to a Modulating Cooling device when you have confi gured

this option for your HVAC unit. If reverse acting is

confi gured, this percentage will be reversed. See the

following examples for clarifi cation:

Standard

Operation:

0-10 VDC

0% = 0 VDC

100% = 10 VDC

2-10 VDC

0% = 2 VDC

100% = 10 VDC

1.5-5.0

VDC 0% = 1.5 VDC

100% = 5.0 VDC

Reverse Acting Operation:

0-10 VDC

0% = 10 VDC

100% = 0 VDC

2-10 VDC

0% = 10 VDC

100% = 2 VDC

If you do not have a

Modulating Cooling device

connected

to your HVAC unit and confi gured, this screen will

indicate [No Mod Cool Confi g].

If this unit has a Dual Digital Module, Full Digital

Module, or Water Source Heat Pump with multiple

Digital Scroll Compressors, this line will be blank.

Line 3 Current Modulating Heating Output Signal Percentage

Indicates the percentage of the output signal being

supplied to a Modulating Heating device when you have

confi gured this option for your HVAC unit. If Reverse

Acting operation is confi gured, this percentage will be

Reversed. See the following examples for clarifi cation: