beautypg.com

Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 62 – Orion System VCM-X/RNE Controller User Manual

Page 62

background image

VCM-X / RNE STATUS

VCM-X / RNE Operator Interface SD

62

VCM-X / RNE Status Screens

Status Screen 21 /

VCM-X

- Full Digital Module

Line 2 Full Digital Temperature

If using a VCM-X E-BUS Modular Controller

with a Full Digital Module (OE370-23-FD-A) or if you are

using the VCM-X E-BUS WSHP Controller with at

least two Digital Scroll Compressors, this screen will

appear. Values will show zero if not using 4 Digital Scroll

Compressors.

Line 3

Coil B1 Temperature

This is the current Coil Suction Temperature of

Compressor

B1.

Line 4

Coil B2 Temperature

This is the current Coil Suction Temperature of

Compressor

B2.

Status Screen 21 / RNE - Full Digital Module

Line 2 Full Digital Temperature

If using a Full Digital Module ( OE370-23-FD-A) or

Water Source Heat Pump Module (OE334-23-WPM-A),

this screen will appear. If not using (2) Full Digital

Modules, this screen will show no values.

Line 3 Coil B1 Temperature

This is the current Coil Suction Temperature of

Compressor

B1.

Line 4 Coil B2 Temperature

This is the current Coil Suction Temperature of

Compressor

B2.

RNE Cnfg ID 102

Full Digital Temp

Coil B1: X.Xº F

Coil B2: X.Xº F

Status Screen 22 / VCM-X - Full Digital Signal

OR Dual Digital Signal

VCMX-M/HP Cnfg ID 102

Full Digital

Stage 1 Sig: 0%
Stage 2 Sig: 0%

Line 2 Full Digital Signal

If using a VCM-X E-BUS Modular Controller

with a Full Digital Module ( OE370-23-FD-A) or if you are

using the VCM-X E-BUS WSHP Controller with at

least two Digital Scroll Compressors, this screen will

appear.

Line 3 Stage 1 Signal Percentage

This is the modulating signal percentage for Compressor

1 (A1) if there are two Digital Scroll Compressors, or for

Compressors 1 (A1) and 3 (B1) if there are four Digital

Scroll

Compressors.

Line 4 Stage 2 Signal Percentage

This is the modulating signal percentage for Compressor

2 (A2) if there are two Digital Scroll Compressors, or for

Compressors 2 (A2) and 4 (B2) if there are four Digital

Scroll

Compressors.

VCMX-M/HP Cnfg ID 102

Dual Digital

Comp A Sig: 0%
Comp B Sig: 0%

Line 2 Dual Digital Signal

If using a VCM-X E-BUS Modular Controller

with a Dual Digital Module ( OE370-23-DD) or if you are

using the VCM-X E-BUS WSHP Controller with two

Digital Scroll Compressors, this screen will appear.

Line 3 Compressor A Signal

This is the modulating signal percentage for Circuit A

Compressor

1

(A1).

Line 4 Compressor B Signal

This is the modulating signal percentage for Circuit B

Compressor

1

(B1).

VCMX-M/HP Cnfg ID 102

Full Digital Temp

Coil B1: X.Xº F

Coil B2: X.Xº F