VCM-X / RNE STATUS
VCM-X / RNE Operator Interface SD
57
VCM-X / RNE Status Screens
Status Screen 4 - Supply Air Temperature &
Setpoint
VCM-X / RNE v1.00
Supply Air.: XX.XºF
Supply Spt.: XX.XºF
Line 2 Current Supply Air Temperature
The Supply Air Temperature is always required. If a
Supply Air Temperature Sensor is not installed, the VCM-X
/ RNE Controller will not operate correctly and will display
0°F.
Line 3
Current Active Supply Air Setpoint
This is the Supply Air Setpoint for the mode that the
unit is currently operating in. If the Supply Air Reset is
confi gured, this is the calculated setpoint based on the
current Reset Source conditions.
Status Screen 5 - Space Temp, Return Air &
Slide Adjust
VCM-X / RNE v1.00
Space Tmp.: XX.XºF
Return Air.: XX.XºF
Slide Adj.: XX.XºF
Line 2
Space Temperature
If you are using a Space Temperature Sensor, this line will
display the current Space Temperature during the Occupied
or
Unoccupied
Mode.
Line 3
Return Air Temperature
This sensor is optional. If a Return Air Temperature Sensor
is not used, it will display 0°F.
Line 4
Slide Adjust
This is the current value of the Space Temperature offset
based on the position of the slide adjust switch on the Space
Sensor.
Status Screen 6 / VCM-X - Leaving Water
Temperature A
VCM-X v1.00
Leaving Water
Temp A: 0.0ºF
Line 2-3 Leaving Water Temperature A
If using the VCM-X Controller and you have a Water
Source Heat Pump Unit installed, this screen will appear
and display the Leaving Water Temperature of the unit. If
this unit has two leaving water temperature sensors, this is
the Leaving Water Temperature of System A.
Status Screen 6 / RNE - Leaving Water
Temperature 1
RNE v1.00
Leaving Water 1
Temp A: 0.0ºF
Temp B: 0.0ºF
Line 2
Leaving Water Temperature 1
If using the RNE Controller and you have a Water Source
Heat Pump Module installed or if there are two Water
Source Heat Pump Modules installed and this is the fi rst
Module, then this screen will display Water Temperatures
of this Module. If not, this screen will display 0°F.
Line 3
Leaving Water Temperature A
This line will display the Leaving Water Temperature of
the
fi rst Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the fi rst sensor on the Module
with
address
1.
Line 4
Leaving Water Temperature B
This line will display the Leaving Water Temperature of
the second Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the second sensor on the
Module with address 1.
Status Screen 7 / VCM-X - Leaving Water
Temperature B
VCM-X v1.00
Leaving Water
Temp B: 0.0ºF
Line 2-3 Leaving Water Temperature B
If using the VCM-X Controller and you have a Water
Source Heat Pump Unit installed with two leaving
water temperature sensors, this screen will display the
Leaving Water Temperature of System B.