VAV/ZONE DAMPER FORCE

75

VAV/Zone Damper Force Modes

Damper Force Modes

Damper Force Modes are available for testing or balancing the system.
These Force Modes can be accessed and programmed from either the
System Manager or Modular Service Tool.

Modular Service Tool Instructions

When using the Modular Service Tool, simply press the

TEST>

key. You will then see the Unit Selection Screen. Enter the unit

ID of the controller you wish to access and press

. You must

type in the number, even if it is “1”. Once communication is established,
the *00* at the bottom will disappear. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication failure

to the controller.

The following screen will be displayed:

Damper Force
Para Blocks

Load / Save / Copy

With the cursor on Damper Force,

press

to access the

Damper Force Mode Screen.

Dampers Force Mode Screen
If the unit ID you entered is for a VCM-X or RNE Controller that has
VAV/Zone Controllers connected to its communication loop, the Damper
Force Mode will act as a “Global” Damper Force Mode. That is, all VAV/
Zone Controllers on that VCM-X or RNE Controller’s communication
loop will be forced to the same Damper Force Mode setting. If the unit
ID you entered is for a VAV/Zone Controller, the Damper Force Mode
setting will only apply to that VAV/Zone Controller.

Damper Force

Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed

Set the appropriate Damper Force Mode by entering numbers 0 through
5. Following is a list of the force modes and their meaning:

0 = Auto

This is the default setpoint. With this setting,

the damper will operate normally and modulate

according to the controller setpoints.

1 = Open

This setting will force the dampers to their fully-

open

position.

2 = Clsd

This setting will force the damper to its fully-

closed

position.

3 = Max

This setting will force the damper to its

Maximum

Position

Setpoint.

See

VAV/Zone

Controller

Setpoint

Screen

#5 on page 69 for

complete

setpoint

information.

4 = Min

This setting will force the damper to its Minimum

Position

Setpoint.

See

VAV/Zone Controller

Setpoint

Screen

#5 on page 69 for complete

setpoint

information.

5 = Fixed

This setting will force the damper to a fi xed

position based on the Fixed Position Setpoint.

See

VAV/Zone Controller Setpoint Screen #8

on page 70 for complete setpoint information.

CAUTION: The Damper Force Modes should only be used

by qualifi ed service personnel. Serious damage to
the ductwork could result if the dampers are all
forced closed and the HVAC unit fan is operating.