Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 59 – Orion System VCM-X/RNE Controller User Manual
Page 59

VCM-X / RNE STATUS
VCM-X / RNE Operator Interface SD
59
VCM-X / RNE Status Screens
Status Screen 11 - Indoor RH & Indoor RH
Setpoint
VCM-X / RNE v1.00
Indoor RH....: XXX%
Indoor RH Spt: XXX%
Line 2 Current Indoor Relative Humidity Percentage
If an Indoor Humidity Sensor has been installed and
confi gured on the unit, the current Indoor Air Relative
Humidity Percentage will appear on this line. The installed
Indoor Humidity Sensor can be either a Wall Mounted type
or a Return Air Mounted type. If an Indoor Humidity
Sensor is not installed, this line will display 0%.
Line 3 Current Indoor Relative Humidity Setpoint Percentage
This is the adjustable Indoor Air Relative Humidity
Setpoint Percentage that has been set by the user.
Status Screen 12 - Static Pressure & Output %
VCM-X / RNE v1.00
Static Pr...: X.XX”
Press Output: XXX%
[Optional Output]
Line 2 Current Static Pressure
Requires the installation and wiring of a Duct Static
Pressure Sensor. If you do not have a Duct Static Pressure
Sensor correctly installed and wired to the controller, this
line will display “0.0”.
Line 3 Current Static Pressure Output Signal Percentage
Indicates the output signal percentage being supplied to the
VFD Controller or Bypass Damper Actuator when you
have
confi gured one of these options for your HVAC unit.
If you have not confi gured Duct Static Pressure Control,
this line will display [No Press Out Confg].
Line 4 Indicates That This is An Optional Output
This output may or may not have live data to display.
Status Screen 13 - Economizer %,
OA Wetbulb, and CO
2
Level
VCM-X / RNE v1.00
Economizer.: XXX %
OA Wetbulb.: XX.XºF
CO2 Level.: XXXXPPM
Line 2 Current Economizer Open Percentage
The Economizer is optional. This shows the Outdoor Air
Damper open percentage. If Economizer Control is not
confi gured, it will display 0%.
Line 3 Current Wetbulb/Drybulb Temperature
The Outdoor Air Wetbulb Temperature is optional. To
display the Outdoor Air Wetbulb Temperature, you must
install an Outdoor Air Temperature Sensor (or an Outdoor
Air Temperature Broadcast) and an Outdoor Air Relative
Humidity Sensor. If these conditions exist, this line will
display
the
calculated
Outdoor
Air
Wetbulb
Temperature.
If these conditions do not exist, it will display 0°F.
Line 4 Current CO
2
Level
The
CO
2
Level is optional. You must install and confi gure a
CO
2
Sensor to display the CO
2
Level. If a CO
2
Sensor is not
installed
and
confi gured, this line will display 0 PPM.
Status Screen 14 - Title 24 Economizer
Feedback Status
VCM-X / RNE v1.00
Economizer
Feedback X%
[Only For Title 24]
Line 3 Economizer Feedback Open Percentage
This shows the Outdoor Air Damper open percentage,
whether the unit is confi gured for Title 24 Economizer
Control or simply has a Minimum Outdoor Air Damper
position
confi gured. If Title 24 Economizer Control is not
confi gured, it will display 0%.
Line 4 Indicates That This is Only For Title 24 Economizer
Status Screen 15 - Outdoor Air CFM & Setpoint
VCM-X / RNE v1.00
OA CFM: 0.00 K
OA Sp.: 0.00 K
[Optional Input]
Line 2 Outdoor Air CFM
If an outdoor air airfl ow monitoring station is being used,
this is the current CFM reading of that device. K = 1000
Line 3 Outdoor Air Setpoint
If control of the OA Damper based on CFM is confi gured,
this is the controlling setpoint. K = 1000
Line 4 Indicates That This is An Optional Input
This input may or may not have live data to display.