VCM-X / RNE SETPOINTS

VCM-X / RNE Operator Interface SD

50

Setpoint Screen #19 - Outdoor Air CFM Control

VCM-X / RNE Spts

OA CFM CONTROL

Min CFM.: 0.10 Kcfm
Max CFM.: 0.10 Kcfm

If controlling the Outdoor Air Damper to a CFM setpoint, this screen
allows you to set the design Minimum and Maximum required Outdoor
Airfl ow CFM values for the Air Handler. The OA Max CFM limits the
damper operation during CO

2

override conditions. K = 1000

Description

Minimum

Default

Maximum

OA Minimum CFM

0.10 Kcfm

.10 Kcfm

200 Kcfm

OA Maximum CFM

0.10 Kcfm

.10 Kcfm

200 Kcfm

Setpoint Screen #20 - Outdoor Air CFM

Deadband

VCM-X / RNE Spts

OA CFM CONTROL

OA CFM DB...: 10CFM

The is the deadband above and below the OA CFM Control Setpoint
which helps prevent hunting.

Description

Minimum

Default

Maximum

OA CFM Deadband

0 CFM

10 CFM

20,000 CFM

Setpoint Screen #21 - Economizer Maximum

Position if High CO

2

Level

VCM-X / RNE Spts

Maximum Economizer

Position if High CO2
Level Occurs.: 100%

This Setpoint allows you to set the Maximum Position the Economizer
will open if high CO

2

conditions occur in the space. The Maximum

Economizer Position Setpoint is used to limit the amount of Outdoor Air
that will be introduced to the HVAC unit in order to ensure the unit is
operating within its Heating and Cooling design limitations. As shown
in the table below, the Minimum setting for this Setpoint is the value
previously set for the Economizer Min Position Setpoint.

Description

Minimum

Default

Maximum

Maximum Economizer

Position If High CO

2

Level Occurs

Economizer

Minimum

Position

100%

100%

VCM-X / RNE Setpoint Screens

Setpoint Screen #22 - CO

2

Protection Limit

VCM-X / RNE Spts

CO2 Protection Limit

Max Level.: 900 PPM
Reset Rnge: 100 PPM

When the CO

2

level rises above the CO

2

Protection Limit Max Level, the

Economizer’s Minimum Position will begin to reset open proportionally
between the CO

2

Protection Limit Max Level Setpoint and the Reset

Range Setpoint. The Reset Range value is added to the Max Level value.
If the CO

2

levels are equal to or above the Max Level plus the Reset

Range, the Economizer will be opened to its Maximum Economizer
Position if high CO

2

levels occur.

Description

Minimum

Default

Maximum

CO

2

Protection Limit

Max Level

0 PPM

900 PPM

3000 PPM

CO

2

Protection Limit
Reset Range

0 PPM

100 PPM

1500 PPM

Setpoint Screen #23 - Static Setpoint,

Deadband & Control Rate

VCM-X / RNE Spts

Static Spt...: 0.50”

Deadband.....: 0.10”
Control Rate.: 10 s

For VAV units, a Supply Fan VFD or Bypass Damper Actuator is used to
maintain the Duct Static Pressure Setpoint. The Static Pressure Output
Signal varies to control the Static Pressure Setpoint. If the Duct Static
Pressure is above the Static Setpoint plus the Deadband, the Static Pres-
sure Output Signal will be reduced at every Control Rate interval. If the
Static Pressure is below the Static Setpoint minus the Deadband, the
Output signal will be increased at every Control Rate interval.

The Duct Static Pressure Control Output Signal is a non-confi gurable
Direct Acting Signal (0-10 VDC). This can be used to directly connect
to a Supply Fan VFD without any modifi cations.

When you are using a Bypass Damper Actuator to control the Duct
Static Pressure, you must set up the Bypass Damper Actuator or the
Bypass Damper so that it is Reverse Acting in operation. The Output
Signal increases (closes Bypass Damper) if the Duct Static Pressure is
below the Duct Static Pressure Setpoint by the Deadband amount and
the Output Signal decreases (opens Bypass Damper) if the Static Pres-
sure is above the Setpoint by the Deadband amount.

Description

Minimum

Default

Maximum

Static Spt

0.10″ WG

0.50″ WG

3.0″ WG

Deadband

0.10″ WG

0.10″ WG

1.0″ WG

Control Rate

1 Sec

10 Sec

30 Sec