beautypg.com

Vav/zone controller programming, Vav/zone setpoint screens, Vcm-x / rne operator interface sd 70 – Orion System VCM-X/RNE Controller User Manual

Page 70

background image

VAV/ZONE CONTROLLER PROGRAMMING

VCM-X / RNE Operator Interface SD

70

VAV/Zone Setpoint Screens

Setpoint Screen #3 - AHU Heat Call Space Temp

XX Box Spts IDXXXX

AHU Heat Call

Space Temp...: XXºF

This setpoint allows you to set a Space Temperature that will cause the
VAV/Zone Controller to send a call for heat to the HVAC unit. This only
occurs in the Unoccupied Mode.

Description

Minimum

Default

Maximum

AHU Heat Call Space Temp

50ºF

70ºF

90ºF

Setpoint Screen #4 - Auxiliary Heat Setpoint

XX Box Spts IDXXXX

Auxiliary Heat

Setpoint..: XXºF

This setpoint allows you to set a Space Temperature that will enable
the Auxiliary Heat Relay (Relay 4) on the VAV/Zone Controller Re-
heat Expansion Board for heating options other than box heat, such as
baseboard heat or an external duct heater. This could control a stage of
electric heat or an on/off hot water valve. The Auxiliary Heat Relay will
energize at .5˚F below this setpoint and will de-energize at .5˚F above
this setpoint. The Auxiliary Heat will continue to function regardless of
the HVAC Mode the unit is in and at any airfl ow condition.

Description

Minimum

Default

Maximum

Auxiliary Heat Setpoint

50ºF

70ºF

90ºF

Setpoint Screen #5 - Damper Airfl ow Integral

XX Box Spts IDXXXX

Damper/Airflow Spt

Integral [Ki]..: XXX

The VAV/Zone Controller normally opens its damper based on a Pro-
portional Error from Setpoint. That means if the zone temperature is 4°F
from setpoint, the damper would be 100% open, or it would be modulat-
ing to provide the Maximum CFM on Pressure Independent boxes. If
the error is less than 4°F, the damper may stagnate at that position and
never satisfy the zone. If you add Integral into the damper calculation
process, this will cause the damper or airfl ow calculations to continue
to increase as long as the zone temperature is still above the setpoint.
That means it can provide 100% or Maximum CFM before the 4°F er-
ror is achieved, bringing the zone under control faster than it normally
would. Start with a small (5 or 10) value, if you use this, and monitor
the effect it has. If you enter too large a value, you can create “hunting”
situations that can cause the damper actuator to prematurely wear out.

Description

Minimum

Default

Maximum

Integral

0

0

100

Setpoint Screen #6 - Damper Airfl ow Max &

Vent Min

XX Box Spts IDXXXX

Damper/Airflow Spt

Maximum..: XXX %

Vent Min.: XXX %

The VAV/Zone Controller will not allow the damper or airfl ow calcula-
tion to exceed the Maximum setpoint while it is allowing the damper to
modulate. During Vent mode when there is no heating or cooling demand,
the damper or airfl ow will maintain at least the Vent Min amount of
airfl ow into the zone for ventilation.

Description

Minimum

Default

Maximum

Maximum

0% or 0 CFM

100% or

1000 CFM

100% or

30000 CFM

Vent Min

0% or 0 CFM

25% or

250 CFM

100% or

30000 CFM

Setpoint Screen #7 - Damper Airfl ow Cool/

Heat Minimum

XX Box Spts IDXXXX

Damper/Airflow Spt

Cool Min.: XXX %
Heat Min.: XXX %

During Supply Air Cooling Mode, if the space being served by this
damper is satisfi ed and has no cooling demand, the damper will close to
this Cool Min setting. This provides a minimum amount of airfl ow into
the space for ventilation, even if the space does not require additional
cooling. During Supply Air Heating Mode, if the space being served
by this damper is satisfi ed and has no heating demand, the damper will
close to this Heat Min setting. This provides a minimum amount of
airfl ow into the space for ventilation, even if the space does not require
additional heating.

Description

Minimum

Default

Maximum

Cool Min

0% or

0 CFM

10% or

1000 CFM

100% or

30000 CFM

Heat Min

0% or

0 CFM

10% or

100 CFM

100% or

30000 CFM