RNE CONFIGURATION

VCM-X / RNE Operator Interface SD

36

RNE Confi guration Screens

Confi guration Screen #3 - HVAC Mode Enable

RNE Cnfg ID 101

HVAC Mode Enable

Supply Air

Use < Or > To Change

Select the Temperature Sensor that will determine the Heating, Cooling,
or Vent Mode of operation. The selections are:

 

Supply Air

This is typical for VAV applications. Occupied Cooling

with

Morning

Warm-up.

Outdoor

Air

This is for 100% Outdoor Air (MUA) units.

Dehumidifi cation utilizes a Dewpoint Calculation if

equipped with an Outdoor Air Humidity Sensor.

Space

Temperature

This is for any unit that conditions a space and is not 100%

Outdoor air. Occupied/Unoccupied Heating, Cooling, and

Vent Modes of operation.

Return

Air

This selection can be used when an Average Building

Temperature (the Return Air Temperature) needs to

determine Heating, Cooling, and Vent Modes of operation.

Supply Air/Tempering

This selection is for VAV “cooling only” applications where

because of cold outdoor temperatures, even at minimum

damper position, you may need to enable heat to maintain

the cooling near its Cooling Supply Air Setpoint. When

heat is enabled during this sequence, it will control to

a non-adjustable setpoint that is 2ºF less than the Cooling

Supply Air Setpoint. Includes a Morning Warm-up

sequence.

Confi guration Screen #4 - HVAC Reset Source

RNE Cnfg ID 101

HVAC Reset Source

No Reset

Use < Or > To Change

The Supply Air Heating and Cooling Temperature Setpoints can be reset
using various input sources. Default is No Reset. Select the desired
Reset Source for Supply Air Temperature Reset. The Single Zone VAV
option should be selected in applications where the Supply Fan VFD
speed is reset based on the Space Temperature. If you select No Reset,
then neither the Supply Air Setpoint nor the Supply Fan VFD Reset will
occur. The selections are:

No Reset

Fan VFD Percentage

Sp

ace Sensor

Outdoor Sensor

Return Air Sensor

Single Zone (SZ) VAV

Remote Reset Signal

SZ VAV with CV Heating

Confi guration Screen #5 - Reset Interval Rate

RNE Cnfg ID 101

Reset Interval

Rate...: 20 s

[1-255 Seconds]

If you selected Space or Return Air Temperature Reset in Screen #4,
enter a value in seconds between 1-255. This value determines how fast
the Supply Air Temperature Setpoint is adjusted as the Reset Source
changes. Default is 20 seconds.

Confi guration Screen #6 - Dehumidifi cation

Control

RNE Cnfg ID 101

Dehumidification

Control: NO

Use < Or > To Change

Select YES if your system requires Dehumidifi cation Control. Default
is NO.

Confi guration Screen #7 - Dehumidifi cation

Priority

RNE Cnfg ID 101

Dehumidification

Priority: NO

Use < Or > To Change

Select YES if Dehumidifi cation is a Priority during the Occupied Mode.
Priority means that the Cooling stages will activate based on Coil Tem-
perature and Reheat will be used regardless of Heating, Cooling, or Vent
Modes of Operation. Default is NO.

Confi guration Screen #8 - Dehumidifi cation

Unoccupied

RNE Cnfg ID 101

Dehumidification

Unoccupied: NO

Use < Or > To Change

Select YES if Dehumidifi cation is required during the Unoccupied
mode. Unoccupied Dehumidifi cation is activated based on Indoor Air
Humidity only. Default is NO.