beautypg.com

Gasboy Islander PLUS User Manual

Page 74

background image

Table 3-2. Islander PLUS Terminal Block -4 Mechanical Pump – Connections Definition

Terminal No.

Signal Name

Functional Description

3

RX-RS232

Receive Data interface

4

RS-485 GND

Data link to Density Probes Console Box /

5

RS-485_+

Density Display

6

RS-485_-

Chassis / Positive / Negative connections

7

PULSER_1

Pulser Input – Nozzle 1

8

PULSER_2

Pulser Input – Nozzle 2

9

PULSER_3

Pulser Input – Nozzle 3

10

PULSER_4

Pulser Input – Nozzle 4

11

GND_1_P

Nozzle Grounding – Nozzle 1

12

GND_2_P

Nozzle Grounding – Nozzle 2

13

GND_3_P

Nozzle Grounding – Nozzle 3

14

GND_4_P

Nozzle Grounding – Nozzle 4

15

+12V_1_P

+12 VDC Output to Pulser – Nozzle 1

16

+12V_2_P

+12 VDC Output to Pulser – Nozzle 2

17

+12V_3_P

+12 VDC Output to Pulser – Nozzle 3

18

+12V_4_P

+12 VDC Output to Pulser – Nozzle 4

19

IN USE 1 A

Handle Up - In Use signal input - Nozzle 1

20

IN USE 2 A

Handle Up - In Use signal input - Nozzle 2

21

IN USE 3 A

Handle Up - In Use signal input - Nozzle 3

22

IN USE 4 A

Handle Up - In Use signal input - Nozzle 4

23

IN USE 1 B(-)

Handle Up – AC In Use signal return - Nozzle 1

24

IN USE 2 B(-)

Handle Up – AC In Use signal return - Nozzle 2

25

IN USE 3 B(-)

Handle Up – AC In Use signal return - Nozzle 3

26

IN USE 4 B(-)

Handle Up – AC In Use signal return - Nozzle 4

27

LINE 1

Pump control 220/110 VAC Input - Nozzle 1

28

LINE 2

Pump control 220/110 VAC Input - Nozzle 2

29

LINE 3

Pump control 220/110 VAC Input - Nozzle 3

30

LINE 4

Pump control 220/110 VAC Input - Nozzle 4

31

LOAD 1

Pump control output - Nozzle 1

32

LOAD 2

Pump control output - Nozzle 2

33

LOAD 3

Pump control output - Nozzle 3

34

LOAD 4

Pump control output - Nozzle 4

35

LINE IN (115/230v)

Line Connection, Islander PLUS power input

36

NEUTRAL IN (115/230v)

Neutral Connection, Islander PLUS power input

Islander PLUS Manual

60

This manual is related to the following products: