beautypg.com

6.3. cables routing, 7. power setup, 7.1. general – Gasboy Islander PLUS User Manual

Page 51: Table 2-2. islander plus, cables type, Table 2-3. islander plus, cables routing

background image

Table 2-2. Islander PLUS, Cables Type

No.

Function

Type

1

AC Power from Office

Power cable, 3x1.5 mm

2

NYY (14 AWG),

in accordance with local standards

Control to pumps (valves or engine)

In-use signal

2

Pulser

Data communication cable, 300 V RMS,
90ºC, shielded twisted pair, oil resistant, 24
AWG, low capacitance below 60 PF/meter
similar to Belden 9729 cable

TLG (RS-232)

3

LAN

CAT5E, Shielded, 300 V RMS, 90ºC
similar to Belden 121700A

4

GND

Ground cable 0.4" (10.8 mm

2

)

2-6.3. Cables Routing

Route the cables from the peripherals and the Office to Islander PLUS as listed in Table 2-3 and
shown in Figure 2-4. Proceed as follows:

Table 2-3. Islander PLUS, Cables Routing

No.

Functional Description

From

Through Insert

Cable Type (*)

1

Power AC

Office

High voltage conduit

1

2

GND

Office

High voltage conduit

4

3

TLG

Office

Low voltage conduit

2

4

LAN

Office

Low voltage conduit

3

5

Control, Pump A

Pump A High voltage conduit

1

6

In-use, Pump A

Pump A High voltage conduit

1

7

Pulser, Pump A

Pump A Low voltage conduit

2

(*) Refer to Table 2-2.

2-7. POWER SETUP

2-7.1. General

The power equipment shall be installed in the Main Power Cabinet of the station office. It should
include the following:

Islander PLUS Manual

37

This manual is related to the following products: