6.3. cables routing, 7. power setup, 7.1. general – Gasboy Islander PLUS User Manual
Page 51: Table 2-2. islander plus, cables type, Table 2-3. islander plus, cables routing

Table 2-2. Islander PLUS, Cables Type
No.
Function
Type
1
AC Power from Office
Power cable, 3x1.5 mm
2
NYY (14 AWG),
in accordance with local standards
Control to pumps (valves or engine)
In-use signal
2
Pulser
Data communication cable, 300 V RMS,
90ºC, shielded twisted pair, oil resistant, 24
AWG, low capacitance below 60 PF/meter
similar to Belden 9729 cable
TLG (RS-232)
3
LAN
CAT5E, Shielded, 300 V RMS, 90ºC
similar to Belden 121700A
4
GND
Ground cable 0.4" (10.8 mm
2
)
2-6.3. Cables Routing
Route the cables from the peripherals and the Office to Islander PLUS as listed in Table 2-3 and
shown in Figure 2-4. Proceed as follows:
Table 2-3. Islander PLUS, Cables Routing
No.
Functional Description
From
Through Insert
Cable Type (*)
1
Power AC
Office
High voltage conduit
1
2
GND
Office
High voltage conduit
4
3
TLG
Office
Low voltage conduit
2
4
LAN
Office
Low voltage conduit
3
5
Control, Pump A
Pump A High voltage conduit
1
6
In-use, Pump A
Pump A High voltage conduit
1
7
Pulser, Pump A
Pump A Low voltage conduit
2
(*) Refer to Table 2-2.
2-7. POWER SETUP
2-7.1. General
The power equipment shall be installed in the Main Power Cabinet of the station office. It should
include the following:
Islander PLUS Manual
37