The types of conduits in the Island are a function of the different equipment, and their location in
the Island. Basically, there are two functional conduits:

• High voltage conduits

• Low voltage conduits

The following conduits are required in the Island:

High voltage conduits

o

AC power for Islander PLUS

o

Pump control from pumps to Islander PLUS

o

Pump In-use signal from pumps to Islander PLUS

Low voltage conduits

o

Internet line from LAN at Office to Islander PLUS

o

RS-232 communication line from TLG at office to Islander PLUS

o

RS-485/422/C.L. or Tokheim

o

Pulser from pumps to Islander PLUS

Grounding

o

At least 10 mm (OOO AWG) Grounding cable to pump chassis

o

At least 10 mm (OOO AWG) Grounding cable to Islander PLUS pole

(Connected to the external chassis grounding post)

o

Grounding cable to TLG – in accordance with TLG manufacturer

instructions.

Tank conduit

o

TLG probe

2-4.5. Required Conduits in Islander PLUS

Four conduits can be inserted in the Islander PLUS, each carrying specific wires, as listed in
Table 2-1 and shown in Figure 2-4.

Table 2-1. Conduits into Islander PLUS

No.

Conduit Type

Type

1

Low voltage

Pulser, TLG, LAN

2

High voltage

AC power, GND , In-use

3

High voltage

Control