Table 5-1. Islander PLUS Troubleshooting (Cont'd)
Fault
Probable Cause
Checks
Corrective Action
Pump is Authorized and refueling but volume remains zero
Pump is refueling
but volume
remains zero
Pulse factor is zero
Check SO pump setup
Change Pump Settings to
correct the factor for the
relevant pump
Faulty MPI-C board
Faulty pulser
Disconnect the pulser and
short the pulse-in wires to
simulate pulses
If pulses are received
during refueling, replace
pump pulser
If not, replace MPI-C board
No control on refueling
Pump is refueling
without any
control
Pump is in bypass
Verify that Islander PLUS
bypass switch is off
Turn bypass switch off, if
on
Faulty SSR
Replace the relevant SSR
unit inside the Islander
PLUS
If an external relay
is used to control
the pump/valve, it
may be stuck due to
a small current leak
Add a snubber (capacitor +
resistor) in parallel to relay
input