TEST_MODE: This variable is bit mapped variable that will allow special tests to be done to the
positioner.
Bit
Test
0
DAC control given to PC, write to DAC_value
1
Blink red LED, used for electronics board test. Bits 2 &
3 may not be set when active
2
Blink yellow LED, used for electronics board test. Bits
1 & 3 may not be set when active
3
Blink green LED, used for electronics board test. Bits
1 & 2 may not be set when active
4
Reserved
5
Reserved
6
Reserved
7
Enable diagnostic scan list
TRAVEL_FLAGS: Each bit within this variable is a flag indicating errors or alerts related to valve
travel. Logic one indicates the flag is active.
Bit
Description
0
0 = No alert
1 = Final_Value_Cutoff active (this can be either high or low)
1
0 = No alert
1 = Lower soft stop active
2
0 = No alert
1 = Upper soft stop active
3
0 = No alert
1 = Lower position alert
4
0 = No alert
1 = upper position alert
5
0 = No alert
1 = Cycle counter limit exceeded
6
0 = No alert
1 = Travel accumulator limit exceeded
7
0 = No alert
1 = Position deviation alert
TRAVEL_UNITS: This is an enumerated byte that indicates the engineering units being utilized for the
travel accumulator and stroke. The unit codes are defined as follows:
47 = inches
49 = millimeters
•
•