Sync and Scheduling Objects
These objects are used by system management to provide application clock synchronization and
macro cycle scheduling for the device. Table 8.25 identifies the sync and scheduling objects with their
object directory index and default values.

Table 8.25 SM Sync and Scheduling Objects

Object

Description

OD

index

Default Value

CURRENT_TIME

The current application clock time.

262

Dynamic

LOCAL_TIME_DIFF

Used to calculate local time from CUR-

RENT_TIME.

263

0

AP_CLOCK_SYNC_

NTERVAL

The interval in seconds between time

messages on the link (bus).

264

Set by SM (mgr.) during

address assignment

TIME_LAST_RCVD

The application clock time contained in

the last clock message.

265

Dynamic

PRIMARY_AP_TIME_

PUBLISHER

The node address of the primary time

publisher for the local link (bus).

266

Set by SM (mgr.) during

address assignment

TIME_PUBLISHER_ADDR The node address of the device which

sent the last clock message.

267

Dynamic

Unused

268

MACROCYCLE_DURA-

TION

The length of the macro cycle in 1/32 of

a millisecond ticks.

269

Set by SM (mgr.) during

address assignment

Device ID, Tag Name and Device Address
Each fieldbus device on the network is uniquely identified by:

Address Assignment Objects

Table 8.26 is a description of the address assignment objects with their object directory index and
default values.

Table 8.26 SM Address Assignment Objects

Object

Description

OD index

Default Value

DEV_ID

The device ID set by the

manufacturer.

270

464C530201-VAL-LX1

400-0nnnnnnnn

PD_TAG

The physical device tag to be set

using SET_PD_TAG service.

271

All Spaces

OPERATIONAL_

POWERUP

Controls the state of SM of the

device upon power-up.

272

TRUE (SM goes opera-

tional after power up)

Device ID that is set by the manufacturer to identify the device.

Device Name (Tag) - set by the user to identify operation

Device Address - a unique numerical address on the fieldbus segment. Address may be set

automatically by system management.