Table 10.3 Device Troubleshooting C

Symptom

• Device output is not updating.

Possible Cause

Items to Check

Recommended Action

Resource block mode is OOS

Read MODE_BLOCK. ACTUAL of

Resource block.

If necessary, set MODE_BLOCK.

TARGET to Auto.

Resource block is not running.

Read the first element of

BLOCK_TEST. Number should be

increasing indicating that block is

running. If block is not running,

check the second element of

BLOCK_TEST.

If second element of BLOCK_TEST

is not zero, write all zeroes to

element.

Check BLOCK_ERR for other

errors.

See Sub-section 10.7 for details

on BLOCK_ERR.

If an error is present in BLOCK_

ERR, then read ERROR_DETAIL.

See Sub-section 10.7 for details

on ERROR_DETAIL parameter.
Set RESTART to processor (or ‘4’)

to soft-restart the device.

Incorrect revision of resource

block firmware.

Read DEV_TYPE , DEV_REV, and

DD_REV.

See Incorrect or non-compatible

tools above in Sub-section 10.3.

Incorrect revision level of the

device firmware.

Read REVISION_ARRAY.

See Incorrect or non-compatible

tools above in Sub-section 10.3.

Transducer block mode is OOS

Read MODE_BLK . ACTUAL.

Set MODE_BLK.TARGET to auto.

NOTE: Transducer block must

be in AUTO mode for the sensor

signal to be passed to ‘AO block.’

Transducer block is not producing

valid primary data.

1. Read the first element of

BLOCK_TEST. Number should be

increasing indicating that block is

running. If block is not running,

check the second element of

BLOCK_TEST.

If second element of BLOCK_TEST

is not zero, write all zeroes to

element.

2. Read BLOCK_ERR.

See Sub-section 10.7 for details

on BLOCK_ERR.

3. Verify parameter FINAL_VALUE

is not valid STATUS = good or

uncertain VALUE = active
4. Read FINAL_POSITION VALUE;

should contain the position. Iso-

late valve from process and check

calibration.

Report information to factory.

Analog Output block mode is OOS Read MODE_BLK.ACTUAL of AO

block.

Set MODE_BLK .TARGET to auto.

AO block is not initialized

1. CHANNEL

1. Set to 1

2. SHED_OPT

2. Set to a value other than Un-

initialized

PID block is not initialized

SHED_OPT

Set to a value other than uniniti-

alized.

PID block mode is OOS

Read MODE_BLK.ACTUAL of PID

block.

Set MODE_BLK.TARGET to Auto.