Flowserve 3400IQ Digital Positioner User Manual
Page 95
![background image](https://www.manualsdir.com/files/784500/content/doc095.png)
Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
flowserve.com
PRESS_FLAGS: Each bit within this variable is a flag indicating parameters relevant to the pressure
sensors (Advanced model ONLY). A logic 1 indicates error is active.
Bit
Description
0
0 = No error
1 = Loss of supply
1
Not used
2
0 = No error
1 = Output port 1 sensor failure (low pressure reading during calibration)
3
0 = No error
1 = Output port 2 sensor failure (low pressure reading during calibration)
4
Not used
5
Not used
6
Not used
7
Not used
PRESS_UNITS: This is an enumerated byte that indicates the engineering units being utilized for
pressure sensor reporting. The embedded code supports units of psig, barg, KPag, and Kg/cm2g.
The unit codes are defined as follows:
6 = psi
7 = bar
10 = Kg/cm2
12 = Kpa
SIG_FLAGS: Byte which will be added to the end of each signature data frame to show progress and
end-of-signature. One flag will set STEP or RAMP STATUS_flags
STATUS_FLAG: Status flag variable for fieldbus. When a bit is set, the corresponding flag variable is
reporting an alarm condition.
Bit
Description
0
0 = No error
1 = Error reported in CALIBRATE flags
1
0 = No error
1 = Error reported in TRAVEL flags
2
0 = No error
1 = Error reported in INTERNAL flags
3
0 = No error
1 = Error reported in PRESSURE flags
4
0 = No error
1 = Communications error
5
Not used
6
Not used
7
Not used
TEMP_UNITS: This is an enumerated byte that indicates the engineering units being utilized for
temperature reporting. The embedded code supports °C and ° F. The unit codes are defined as
follows:
32 = °C
33 = °F
•
•
•
•
•
•