Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
Clearing Block Configuration Errors
Block	configuration	errors	prevent	the	block	from	leaving	OOS	mode.	The	parameter	BLOCK_ERR	
will	show	whether	a	block	configuration	error	is	present.	Table	10.7	is	a	list	of	parameters	that	can	
cause	the	status	of	CONFIGURATION	ERROR	to	be	set	in	the	AO	BLOCK_ERR	parameter.
NOTE:	CONFIGURATION	ERROR	can	only	be	cleared	if	the	function	block	is	being	executed.	One	
way	of	determining	block	execution	is	by	performing	a	series	two	or	three	reads	of	the	BLOCK_TEST	
parameter	and	confirming	that	the	first	byte	of	the	parameter	is	incrementing.	This	will	work	if	the	
execute	rate	is	fast	relative	to	the	speed	of	reading	BLOCK_TEST.	A	very	slowly	executing	block	may	
not	appear	to	execute	because	block	parameters	are	updated	only	when	the	block	executes.
Parameter
Initial Value
Valid Range
Corrective action
CHANNEL
0
1
Initial value is a configu-
ration error. Set value in
valid range.
SHED_OPT
0
1-8 (see Shed Options in
the FF specs.)
Initial value is a configu-
ration error. Set value in
valid range.
SP_HI_LIM
SP_LO_LIM
100 0
PV_SCALE +/- 10%
Verify that SP_HI_LIM >
SP_LO_LIM.
Mode-restricted Write Operations
Table	8.7	lists	the	AO	block	parameters	which	may	be	write	restricted	based	upon	the	block’s	mode.	
Listed	in	the	table	are	the	TARGET	and/or	ACTUAL	modes	required	for	the	write	to	be	accepted.	Other	
limitations	listed	in	the	last	column	must	also	be	met.
SIMULATE, READBACK and PV Determination
In	the	AO	Function	Block,	these	three	parameters	provide	the	values	and	status	of	the	actuator	
position,	where	SIMULATE	(or	optionally	OUT)	generates	the	READBACK	parameter	and	READBACK	
is	then	re-scaled	to	produce	the	PV.
The following sub-sections describe each of these parameters.
SIMULATE Parameter SIMULATE	is	the	interface	parameter	between	the	AO	and	the	Transducer	
Function	Blocks.	Each	time	the	AO	block	executes,	SIMULATE.TRANSDUCER	is	updated	with	the	
FINAL_POSITION_VALUE	from	the	transducer	block.
When	the	SIMULATE.ENABLE	is	FALSE,	SIMULATE.TRANSDUCER	is	copied	into	SIMULATE.
SIMULATE.	When	SIMULATE.ENABLE	is	TRUE,	SIMULATE.SIMULATE	is	not	updated	with	
SIMULATE.TRANSDUCER	and	the	user	may	write	a	value	and	status	to	SIMULATE.SIMULATE.
NOTE:	SIMULATE.ENABLE	can	only	be	set	TRUE	when	the	Simulate	dip	switch	is	in	the	“On”	position	
when	the	device	is	powered	up	or	a	processor	restart	is	issued.
READBACK Parameter The	value	and	status	of	READBACK	will	come	from	either	the	OUT	
parameter	or	SIMULATE.SIMULATE,	determined	by	the	state	of	the	OUT_READBACK	feature	in	the	
Resource	Block.	READBACK	is	in	XD	units.
When	RS.FEATURE.OUT_READBACK	is	set	TRUE,	SIMULATE.SIMULATE	is	used	for	READBACK.	
When	FEATURE.OUT_READBACK	is	FALSE,	OUT	will	be	used	for	READBACK.
NOTE:	The	default	value	for	RS.FEATURE.OUT_READBACK	is	FALSE.	With	the	Logix	3400IQ,	this	
feature	should	always	be	set	TRUE	to	allow	the	transducer	block	position	value	to	be	the	source	of	
READBACK.
READBACK_OUT ALLOWS THE USER A LINKABLE PARAMETER FOR VALVE POSITION.
PV Parameter The	PV	value	is	simply	the	READBACK	value,	re-scaled	from	XD	units	to	PV	units.	
PV	status	is	copied	directly	from	READBACK	status.