10.6 Clearing Block Configuration Errors
Clearing Block Configuration Errors
Table	10.8	and	Table	10.9	list	the	parameters	in	the	AO	and	PID	blocks	which	can	cause	the	status	
bit	of	block	configuration	error	to	be	set	in	their	respective	BLOCK_ERR	parameters.	The	tables	also	
provide	the	initial	values	and	the	valid	range	for	the	parameters.
NOTE:	Block	configuration	errors	can	only	be	cleared	if	the	function	block	is	being	executed	
(running).	One	way	of	determining	block	execution	is	by	doing	a	series	of	two	or	three	reads	of	the	
BLOCK_TEST	parameter	and	confirming	that	the	first	byte	of	the	parameter	is	incrementing.	This	will	
work	if	the	execute	rate	is	fast	relative	to	the	speed	of	reading	BLOCK_TEST.	A	very	slowly	executing	
block	may	not	appear	to	execute	because	block	parameters	are	updated	only	when	the	block	
executes.
Table 10.8 AO Block Parameters
Parameter
Initial Value
Valid Range
Corrective Action
ALERT_KEY
0
non-zero
Initial value is a configuration
error. Set value to non-zero
number.
SIMULATE
1 (disabled)
1-2 (disabled -enabled)
Set value in valid range.
XD_SCALE
0 to 100
EU_100 > EU_0, UNITS_
INDEX matches output of
transducer block
Set values to valid range(s).
CHANNEL
0
1-2
Initial value is a configuration
error. Set value to valid range.
SP_RATE_DN
SP_RATE_UP
+INF
0-15
Set value to valid range.
SP_HI_LIM,
100
0-100
Set value to valid range.
SP_LO_LIM
0
0-100
Set value to valid range.
SHED_OPT
0
1-8 (see Shed Options in the
FF specs.)
Initial value is a configuration
error. Set value in valid range.
BYPASS
0
1:OFF, 2:ON
Initial value is a configuration
error. Set value in valid range.
SHED_OPT
0
1-8 (see Shed Options in the
FF specs.)
Initial value is a configuration
error. Set value in valid range.
HI_HI_LIM HI_LIM
+INF	
+INF	
PV_SCALE, +INF
Values must be set in rank order
(e.g. LO_LIM > LO_LO_LIM but <
HI_LIM etc.)
LO_LIM LO_LO_LIM
-INF
-INF
PV_SCALE, -INF
Values must be set in rank order.
OUT_HI_LIM
OUT_LO_LIM
100
0
OUT_SCALE +/- 10%
Verify that OUT_HI_LIM >
OUT_LO_LIM.
SP_HI_LIM SP_LO_LIM
100
0
PV_SCALE +/- 10%
Verify that SP_HI_LIM >
SP_LO_LIM.