Flowserve 3400IQ Digital Positioner User Manual
Page 49
4
Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
flowserve.com
Table 8.5 Transducer Block Parameters
In-
dex
Fieldbus Parameter Name
Fieldbus
Datatype
Storage
Read/ Write
Access
Type
Notes, Default
Values
141
CAL_FULLSCALE
UINT 16 w/
status
S
R/W
142
AUTO_TUNE_MULT
float w/
status
S
R/W
143
NVRAM_WRITE_CYCLES
Unsigned 32 N
R
144
GENERIC_PARM_NUM
DS-66
D
R/W
Honeywell
sts: type
val: Logix Var
Num
145
GENERIC_PARM_VAL
Unsigned32 D
R/W
Honeywell
146
SPI_TEST_RCV
Unsigned8[] D
R
Honeywell
147
SPI_TEST_TX
Unsigned8[] D
R
Honeywell
148
BLOCK_TEST
Unsigned8[] D
R/W
Honeywell
* Must be out-of-service to write.
** After parameters have been changed, it is necessary to perform an update to activate. If an update is not
performed when the parameters have been changed the parameters will be updated during the next update
cycle.
Access Type
NOTE: How the Fieldbus board accesses the respective Control board variable.
Std — Standard Parameters. These values are constantly updated from the Control Board, except
during the ‘Signature’ capture.
Info — Device Information Parameters. These values are read only at start-up or when any of them
are changed. The number -n is used to group parameters into manageable sizes.
Diag — Advanced Diagnostic Parameters. These values are active only when the parameter ‘Enable
diagnostic Variable Access’ is set in TEST_MODE.
Transducer Block Diagram
Figure 8.2 is a block diagram showing the basic components of the transducer block.
Figure 8.2 Transducer Block Diagram
Transducer Block Valtek Product-defined Parameters
Table 8.6 describes the Logix parameters included in the transducer block
Table 8.6 Transducer Block Parameter Descriptions
Parameter
Default Value
Function
MODE_BLK:TARGET
OOS
Determines the mode of the function block
FINAL_VALUE
No default
Command going to positioner before characterization,
soft stops or MPC.
•
•
•
Controller Board