Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
24
Figure	4.1	illustrates	typical	mounting	area	considerations	to	make	before	installing	Logix	3400IQ	
digital	positioner.
Figure 4.1 Typical Mounting Area Considerations Prior to Installation
Temperature Limits 
Table	4.1	lists	the	operating	temperature	limits	for	Logix	3400IQ	digital	positioner.
Power Requirements
The	Logix	3400IQ	digital	positioner	is	a	bus-powered	(two-wire)	device,	meaning	that	it	receives	its	
power	from	the	VDC	on	a	fieldbus	wiring	segment.	Certain	guidelines	and	limitations	exists	regarding	
the	wiring	of	fieldbus	devices.	See	Section	5.4	for	more	information	on	wiring	the	device.
Table 4.2 lists the operating power requirements for the Logix 3400IQ digital positioner.
Table 4.2 Logix 3400IQ Power Requirements
Static Power
Minimum
Maximum
9 VDC @ 23mA
32 VDC @ 23mA
Air Supply Requirements
The Logix 3400IQ digital positioner requires an external air filter (preferably the Valtek coalescing 
air filter).	
The air supply should conform to ISA Standard S7.3 (with a dew point at least 18 °F (10°C) below
ambient temperature, particle size below one micron, and oil content not to exceed one part per
million). For a model with advanced diagnostics (Logix 341X digital positioner), the internal pressure
sensors are rated for continuous operation up to 150 psig.
Minimum supply pressure for proper operation is 30 psig.
Use of a regulator is highly recommended as it aids in the use of the diagnostics feature.
Table 4.1 Operating Temperature Limits
Ambient Temperature
For Intrinsically Safe
Applications
Electronics Ratings
for Explosion-proof
Applications
Mechnical Rating
°C
°F
°C
°F
°C
°F
Logix 3400IQ digital positioner
-4 to 60
-20 to 140
-40 to 55 -40 to 131
-40 to 80
-40 to 176