Flowserve 3400IQ Digital Positioner User Manual
Page 54
![background image](https://www.manualsdir.com/files/784500/content/doc054.png)
Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
4
Fail-safe Handling
The fail-safe parameters determine the response of an output block to the following conditions.
FSTATE_TIME is the number of seconds without communication or with Initiate Fail Safe at the
CAS_IN status, required to put this block into the fail safe state. The FAULT_STATE parameter of the
resource block may also put this block into the fail safe state. The Failsafe Type I/O option determines
whether the action is simply to hold, or to move to FSTATE_VAL.
The Target to Manual if IFS I/O option may be used to latch the fail safe state when IFS appears in the
CAS_IN status. This will cause a fail-safe block alarm. After the cause of the IFS status is removed,
the target mode may be returned manually to CAS mode when it is safe to do so.
AO Block Parameter List
Table 8.7 lists the block parameters and default values for the AO function block.
Table 8.7 AO Function Block Parameter List
Block
Index
Name
Store
Type
Data Type
(Units)
Valid
Range
Write Restrictions
Default Value
1
ST_REV
S
Unsigned16
Read Only
0
2
TAG_DESC
S
Octet String
All spaces
3
STRATEGY
S
Unsigned16
0
4
ALERT_KEY
S
Unsigned8
0
5
MODE_BLK
Mix
MODE_BLK
Target = OOS
Permitted = OS + MAN
+ AUTO + CAS + RCAS
Normal = AUTO
6
BLOCK_ERR
D
Bit String
Read Only
7
PV
D
ANALOG (PV)
Read Only
8
SP
N
ANALOG (PV)
PV_SCALE,
+/- 10%
Target mode must be AUTO,
CAS or RCAS, not permitted
during cascade initialization,
tracking cannot be operative.
9
OUT
N
ANALOG (XD)
XD_SCALE,
+/- 10%
Target mode must be Man
or OOS
10
SIMULATE
D
SIM_FLOAT
Enable = OFF
11
PV_SCALE
S
SCALING
Actual mode must be Man
or OOS
0 – 100
12
XD_SCALE
S
SCALING
Actual mode must be Man
or OOS
0 – 100
13
GRANT_DENY
D
ACCESS_
PERM_T
14
IO_OPTS
S
Bit String
Target mode must be OOS
0
15
STATUS_OPTS
S
Bit String
Target mode must be OOS
0
16
READBACK
D
ANALOG (XD)
Read Only
17
CAS_IN
N
ANALOG (PV)
18
SP_RATE_DN
S
Float (PV /
seconds)
Positive
+INF
19
SP_RATE_UP
S
Float (PV /
seconds)
Positive
+INF
20
SP_HI_LIM
S
Float (PV)
PV_SCALE,
+/- 10%
100
21
SP_LO_LIM
S
Float (PV)
PV_SCALE,
+/- 10%
0
22
CHANNEL
S
Unsigned16
Must be 1
Target mode must be OOS
0
23
FSTATE_TIME
S
Float (seconds)
Positive
0
24
FSTATE_VAL
S
Float (PV)
PV_SCALE,
+/- 10%
0
25
BKCAL_OUT
D
ANALOG (PV)
Read Only
26
RCAS_IN
N
ANALOG
(PV)
27
SHED_OPT
S
Unsigned8
1 to 8
0
28
RCAS_OUT
D
ANALOG (PV)
Read Only
29
UPDATE_EVT
D
EVENT
30
BLOCK_ALM
D
ALARM_
DISCRETE
32
WSP*
D
ANALOG (PV)