beautypg.com

Flowserve 3400IQ Digital Positioner User Manual

Page 135

background image

3

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

Table 11.4 Logix 3400IQ-011 : PID-011 (PID)

Configuration File Data

Comments

(1) ST_REV = 0x0002

Block tagname (PID Control Block)

(index) Paramter mnemonic = value

(2) TAG_DESC =
(3) STRATEGY = 0x0000
(4) ALERT_KEY = 0x00
(5) MODE_BLK =

TARGET = Auto

ACTUAL = Auto

PERMITTED = ROut | RCas | Cas | Auto | Man | OOS

NORMAL = Auto

(6) BLOCK_ERR = 0x0000
(7) PV =

STATUS = Good_Cascade::NonSpecific:NotLimited

VALUE = 0

(8) SP =

STATUS = Good_Cascade::NonSpecific:LowLimited

VALUE = 0

(9) OUT =

STATUS = Good_Cascade::NonSpecific:NonLimited

VALUE = 0

(10) PV_SCALE =

EU_100 = 100

EU_0 = 0

UNITS_INDEX = 0x0000

DECIMAL = 0x00

(11) OUT_SCALE =

EU_100 = 100

EU_0 = 0

UNITS_INDEX = 0x0000

DECIMAL = 0x00

(12) GRANT_DENY =

GRANT = 0x00

DENY = 0x00

(13) CONTROL_OPTS = 0x0000
(14) STATUS_OPTS = 0x0000
(15) IN =

STATUS = Good_NonCascade::NonSpecific:NotLimited

VALUE = 0

(16) PV_FTIME = 0Sec
(17) BYPASS = Off

Initialized value = uninitialized, must be set to valid value

(18) CAS_IN =

STATUS = Good_NonCascade::NonSpecific:NotLimited

VALUE = 0

(19) SP_RATE_DN = 1.#INFPV/Sec
(20) SP_RATE_UP = 1.#INFPV/Sec