9 link objects – Flowserve 3400IQ Digital Positioner User Manual
Page 69
Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
flowserve.com
Notes for Transducer Blocks, all releases:
1. Diagnostic Parameter. This parameter is only accessible if TEST_MODE bit 7 ‘Enable Diagnostic
Scan List’ is set.
2. DAC_VALUE can only be written if TEST_MODE bit 7 AND bit 0 ‘Write to DAC_Value’ are set.
3. Parameter may not be written if SIG_FLAGS bit 0 ‘BEGIN_SIG’ is set. (The Signature Analysis
program is running.)
4. 0x00 if the positioner is a standard model. Advanced Model if the positioner is an advanced type
(pressure sensors). This is determined from hardware settings at start-up
5. This enumeration shows ‘Uninitialized’ when value is 0.
Table 8.14 Analog Output Function Block Parameter Summary
Parameter
Mnemonic
Obj
Type
Data Type
Use/Model
Store Size Valid
Range
Initial
Value
Units Perm. Mode Other
Range
Check
OUT
F
Value and
Status - float
C/Contained N
4
0
BLOCK_TEST A [8] Unsigned8
C/Contained D
8
WSP
S
DS-65
C/Contained D
5
PV_SCALE 0
Read-only
Table 8.15 PID Function Block Parameter Summary
Parameter
Mnemonic
Obj
Type
Data Type Use/Model
Store Size
Valid
Range
Initial
Value
Units Perm.
Mode Other
Range
Check
PID_FORM
S
Unsigned8 C/Contained S 1
1: Ideal
2:Robust
1
enum
MAN
ALGO_TYPE S
Unsigned8 C/Contained S 1
1: A,
2: B
3: C
0
enum
MAN
OUT_LAG
S
Float
C/Contained
S
4
0
sec.
TUNE
MAN Positive
GAIN_NLIN S
Float
C/Contained
S
4
0
TUNE MAN
GAIN_
COMP
S
Float
C/Contained
D
4
0
Read-
only
ERROR_
ABS
S
Float
C/Contained
D
4
PV
Scale
0
PV
Read-
only
WSP
R
DS-65
C/Contained
D
5
PV
Scale
0
PV
Read-
only
BLOCK_
TEST
A [8] Unsigned8 C/Contained
D
8
8.9 Link Objects
Background
The function blocks configured to control a process are linked, or connected by objects within the
devices. These links allow the user to transfer process and event data from one block to another. These
links are defined through link objects.