5 block configuration errors – Flowserve 3400IQ Digital Positioner User Manual
Page 107
07
Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07
flowserve.com
ERROR_DETAIL Enumeration
Table 10.6 lists the enumerated values for the error type element only. The location and sub-type
elements have no significant meaning for users.
Table 10.6 ERROR_DETAIL Parameter Enumeration
ERROR_DETAIL
Message
0
No error
1
Control board ROM checksum
2
HC16 boot ROM checksum
3
HC16 application ROM checksum
4
Interprocessor error (startup)
5
Interprocessor error (operation)
6
EEPROM corrupt (background diagnostics)
7
EEPROM driver error
8
EEPROM - fieldbus write
9
Sensor error
10
Internal software error
11
Other
Using ERROR_DETAIL for Troubleshooting
If a critical error occurs in the resource block, the user should read and record the ERROR_DETAIL
value. Then reset the device (write RESTART parameter Processor). Wait 30 seconds after reset and
read ERROR_DETAIL again to check if error cleared.
10.5 Block Configuration Errors
Configuration Errors
Block configuration errors prevent a device block from leaving OOS mode. The BLOCK_ERR
parameter (bit 1) shows whether a block configuration error is present. Table 10.7 summarizes the
conditions that may be the result of block configuration errors, which in turn cause a device fault.
Follow the recommended actions to correct these errors.
Table 10.7 Summary of Configuration Errors
Problem/Fault
Probable Cause
Recommended Action
Name of parameters
are not visible
Missing or incorrect version of device
description file on host computer.
1. Check path to device description.
2. Load correct version of DD.
Unable to write
successfully to
MODE_BLK of any
block.
Mode not supported in TARGET and/or
PERMITTED modes for the given block.
• Verify that the mode being written is
supported by the block.
• If writing TARGET mode only, then the
desired mode must already be set in
the PERMITTED field.
• If writing the whole MODE_BLK
record, then the mode set in TARGET
must also be set in the PERMITTED
field. Other modes may also be set in
the PERMITTED field, but target mode
must be set.
Unable to write to a
parameter
1. Parameter is read-only.
1. None
2. Sub-index of the parameter is read-only.
Some parameters have fields that are not
writable individually (such as MODE_BLK.
ACTUAL).
2. None