MBT-5000 L-Band Up/Down Converter System
MN-MBT5000
Installation
Revision 4
2–2
Once opened, inspect the shipment:
Step
Task
1
Keep all shipping materials.
2
Check the packing list to make sure the shipment is complete.
3
Inspect the equipment for damage. If damage exists, immediately contact the carrier
and Comtech EF Data to submit a damage report.
4
Read the manual.
2.2
Install the Unit Into a Rack Enclosure
Install the MBT-5000 in its assigned position in the rack enclosure (Figure 2-2). Use, as required:
• A standard rack-mounted shelf;
• User-supplied screws to secure the front panel to the rack enclosure threaded front
mounting rails;
• Comtech EF Data’s optional KT/6228-2 (4”) or KT/6228-3 (10”) Rear-Mounting Support
Brackets Kit (Figure 2-3);
• Comtech EF Data’s optional FP/SL0006 (26”), FP/SL0007 (24”), or FP/SL0008 (22”)
Bearingless Rack Slide Set (Figure 2-4).
For information about custom rack enclosures and these optional installation accessories,
contact Comtech EF Data Product Support.
CAUTION – OBSERVE THE FOLLOWING:
• CORRECT GROUNDING PROTECTION IS REQUIRED TO PREVENT PERSONAL
INJURY AND EQUIPMENT DAMAGE.
You must make sure the ground stud on the rear panel of the unit is always
connected to the protective earth.
• SUFFICIENT AIR VENTILATION IS REQUIRED – Make sure there is adequate air
ventilation clearance inside the enclosure, especially at the side. In a rack system
where there is high heat discharge, provide forced-air cooling with top- or
bottom-mounted fans or blowers.
• MAXIMUM AIR TEMPERATURE – Make sure the air temperature inside the
enclosure
never
exceeds 50°C (122°F).