beautypg.com

5 checklist - startup, 0 commissioning and startup (cont’d) – Reznor YDSA Unit Installation Manual User Manual

Page 66

background image

Form I-Y, P/N 273646R6, Page 66

Power Supply Voltage

Phasing

IMPORTANT: All

refrigeration checks

must be made by

a qualified R-410A

refrigeration

technician.

Fan Rotation

- If fan rotation is not correct, reverse by interchanging two wires on the

3-phase field supply connection. (See Paragraph 7.2.)

Compressors

Connect refrigerant pressure gauges to the suction and discharge lines of the

compressors and an electric meter to the power supply.

CAUTION: Be sure to connect pressure gauges to the suction

and discharge lines before system startup so that compressor

rotation can be checked immediately. Scroll compressors will be

destroyed if allowed to operate in the wrong direction.

Record the ambient temperature. Adjust the system controller so that a call for

cooling exists.

N

OTE: Outdoor ambient lockouts may prevent mechanical cooling. Temporarily

override lockouts by lowering the cooling setpoint. When testing is complete, reset

the controller.

Because it is possible to unknowingly connect 3-phase power in such a way

as to cause the scroll compressor or blower to rotate in reverse, it is very

important to check this on startup. See below and Paragraph 7.2.3.
Check Compressors - Immediately at startup, observe the gauges. If the

suction pressure rises and discharge pressure drops, the compressor is

operating in reverse and must be shut down. Turn off the power and switch

the 3-phase line voltage wiring connections before restarting the unit.

(Important NOTE: If allowed to operate for several minutes in reverse, the

compressor’s internal protector will trip. If a compressor is repeatedly allowed to

restart and run in reverse, the compressor will be permanently damaged.)

If the system is equipped with an optional hot gas bypass, check the valve. Follow

the instructions in Paragraph 7.8.

If the system is equipped with an optional dirty filter switch(es), set the switch(es).

Follow the instructions in Paragraph 8.1.2.

10.5 Checklist -

Startup

10.5.1 System Startup

Assumptions:

All prior-to-startup checks including Test Mode and setting CFM have

been completed satisfactorily and all doors are closed. Compressors with crankcase

heaters have been allowed to warm up for at least 24 hours.
NOTE: Verify startup procedures when the cooling season begins. See maintenance

procedures in Form O-Y.

If there is a gas heat section, turn on the gas.

Adjust the system controller so that a call for cooling exists. Observe for complete

sequencing.

CAUTION: Crankcase heaters must be allowed to warm up for at

least 24 hours prior to startup. Disable cooling controls before

turning on power to warm up crankcase heaters.

10.5.2 Startup Checklist

for Unit with a Gas Heat

Section

Establish a call for heat. Observe for changeover and complete sequencing.

Sequence of Gas Heat Operation:

NOTE: Outdoor ambient lockouts will prevent mechanical gas heating. Temporarily

override lockouts by raising the cooling mode lockout setting to 95°F and the discharge

air heating setpoint to 95°F. When testing is complete, reset set points as required by

the application. (For instructions on changing settings on the programmable control,

refer to Form CP-Y-D19 or CP-Y-D21 in the Literature Bag.)

10.0 Commissioning and Startup (cont’d)

This manual is related to the following products: