Form I-Y, P/N 273646R6, Page 57

Freeze Resistant Trap, P/N 271064, is shipped with

the unit to be installed in the condensate drain.

It is mandatory that the drain be run through the inside

of the roof curb and into the heated space. The drain

must always be installed in a space that remains above

32°F(0°C).

NOTE: All PVC drain pipe is provided by the installer.

Since this drain will be used during the heating season, it is mandatory that the drain

be run through the inside of the roof curb and into the heated space. The drain must

always be installed in a space that remains above 32°F(0°C). Refer to

FIGURE 29A,

shown below

and FIGURE 29B, page 58 and follow the instructions below to install

the condensate drain including the freeze-resistant trap.

If additional frost protection

Option FB1 is being installed, follow the instructions that are provided with the heat

tape. A 115V power supply is required.
If a condensate neutralizer kit Option CSN1 is being installed, follow the instruc-

tions provided with the kit. When a condensate neutralizer is used, an overflow must be

provided so that the condensate will be directed to the drain in the event the neutralizer

becomes plugged. Install a barb “T” in the drain line prior to the inlet of the neutralizer

and run a clear flexible PVC line from the horizontal outlet of the barb “T” to the drain.

Follow the manufacturer’s instructions to recharge the neutralizer tube.
A condensate disposal system that relies on gravity should be satisfactory for most

installations since units are normally installed on the roof.

If a gravity system is not

possible, install an Option CSP1 condensate pump. Follow the pump manufactur-

ers instructions included with the pump. The pump requires a 115V electrical supply.

FIGURE 29A - Location of the Condensate Drain Connection(s) in a High Efficiency Heat Section

(Dual heat section is illustrated.)

= Field-supplied 1/2” PVC pipe(s)

Condensate

Drain Pressure

Switch Tap

Condensate

Drain Pressure

Switch Tap

High-Efficiency

Vent(s)

For units with one heat section (Sizes G150, G225,

and G300), follow the instructions in FIGURE 29B to

install the freeze-resistant trap.

For units with two heat sections (Sizes G302, G372, and G452), join the two PVC drain

pipes with a tee before installing the trap. Follow the instructions in FIGURE 29B.

Drain Connection(s)

(

NOTE: If any of these

condensate drain

accessories (neutralizer kit,

condensate pump, or frost

protection) are required but

were not ordered with the

unit, contact your distributor.

Condensate Drain

Requirements and

Accessories