FIGURE 23 - Manifolds with

Staged Control Option AG71

(2-stage control, single heat

section) and Option AG72

(4-stage control, dual heat

sections)

Flue

Collection

Box

Venter

Assembly

Single Heat Section

Manifold Assembly with

2-Stage Option AG71

Optional

Low Gas

Pressure

Switch

Optional

High Gas

Pressure

Switch

2-Stg

Gas

Valve

Ignitor

Limit

Manifold Pressure Tap

Optional High Gas

Pressure Switch

Ignitor Limit

Venter

Assembly

Dual Heat Section

Manifold Assembly

with 4-Stage

Option AG72

Manifold Pressure Tap

Heat Section 2

Manifold Pressure Tap

Heat Section 1

Venter

Assembly

2-Stg

Valve

Optional

High Gas

Pressure

Switch

2-Stg

Valve

Optional Low

Gas Pressure

Switch

Ignitor

Limit

NOTE: The manifolds

illustrated are for standard

efficiency, non-condensing

heat sections. Follow the

same steps for measuring

manifold pressure on high

efficiency, condensing

heat sections.

Measuring Manifold Pressure

Measuring manifold gas pressure cannot be done until the heater is in operation. It is

a procedure step included in the “Checklist - Startup” steps, Paragraph 10.5.2. When

performing this Startup Step, select and follow the instructions that apply to the gas

control option on the unit.
• Two and Four Stage Options AG71 and AG72 (apply to Model YDSA only)
• Electronic Modulation Control Options AG73 and AG74 (apply to Models YDHA,

YDMA, and YDSA)

Gas pressure measurements should be done with a digital manometer. Two manom-

eters may be required.
IMPORTANT NOTES: On units with two heat sections, take gas pressure measure-

ments with both sections in operation.
Manifold pressure should be as shown in the table on page 49 for the model size, gas

type, and gas control option or as noted on the rating plate.

WARNING

Manifold pressure must never exceed the value listed in the

table on page 49 (or as shown on the rating plate).

9.2.2 Checking

Gas Pressure

(cont’d)

NOTE: If unsure of the

Gas Control Option Code

(AG71, AG72, AG73, or

AG74), check the wiring

diagram on the heater.

All option codes affected

by electrical power are

listed on the bottom of the

wiring diagram after the

unit Model and Size.