Form I-Y, P/N 273646R6, Page 10

5.0 Mounting

5.1 Unit Weights

For unit weights and or corner weights, refer to www.ReznorHVAC.com or call 1-800-695-1901. Specific unit weights

will be supplied by order number which will include the weights of the options specified for that specific unit.

5.2 Curb Cap Base

and Mounting

These packaged systems have a

curb cap base designed for use with

a full perimeter curb. When on a roof,

either a manufacturer-designed roof

curb or a field-supplied roof curb is

required.
NOTE: A Reznor

®

designed roof

curb with integral vertical duct

work supports is recommended to

provide a weatherproof installation.

Base design varies by cabinet size.

MUST be sealed

between curb cap

rail and roof curb.

Optional or

Field-Supplied

Roof Curb fits

under and inside

the curb cap.

Base of curb cap edge

Edge of curb cap

extends down over

the roof curb.

Cabinet W

all

Curb

Cap Rail

Curb Cap

Section

View

5.3 Mounting on a Roof Curb

Two types of fully enclosed curbs are available with these systems.

Roof

Curbs

Option Optional Energy

Recovery Wheel Description

CJ31

No

16” (406mm), Down Discharge with

Duct Supports in the Curb

CJ34

Yes

CJ48

No

36” (914mm), Horizontal Discharge

with Duct Connections in the Curb

CJ55

Yes

If the application is sound sensitive, consider installing a field-supplied vibration iso-

lation curb or specialty sound attenuation curb. Whether using an optional roof curb

available with the system or a field-supplied speciality curb, the curb must be secured,

on square, and level. When the unit is being placed on a roof, location depends on the

roof structure and is the responsibility of the installer. For condensate drainage and

proper operation, it is important that the installation be level.
When positioning the curb, always comply with the required clearances in Paragraph

4.1. Check the dimensions carefully, remembering that the condenser section will

extend 30” (762mm) beyond the edge of the curb. (See orientation in

FIGURE 13,

page 19). Position the curb so that the outside air inlet of the unit will not be facing into

the prevailing wind.
Duct Connections - Optional down discharge roof curbs are designed for duct work

to be inserted in the duct connection opening(s) from above the curb prior to setting

the unit on the curb.