Form I-Y, P/N 273646R6, Page 30

Option BE17

Field Installed in the supply

air duct

Smoke Detector, P/N 159553,

Sampling Tube, P/N 259069

Wiring Connections -

DDC Monitored Smoke

Detector (photoelectric),

Option BE17, P/N 259076

12

24V

9

C

10

NC

OPTION BE17 - SMOKE DETECTOR

6

16

98

BL

*

IF SMOKE DETECTOR IS INSTALLED

*

REMOVE BLUE JUMPER

13

Option GF1

Wiring Connections

- Damper Positioning

Control from an External

0-10V Input Signal (field

provided), Damper

Control Option GF1

Option BE15 or

Option GF8

Wiring Connections - CO2 Sensor (Range 0-2000 ppm), Option BE15

and required for CO2 Sensor included in Damper Control Option GF8

(0-10V)

MANUAL

TO CUSTOMER'S

DAMPER CONTROL

{

U3

GND

CONTROL MODULE

OPTION GF1

97

FIRESTAT, OPTION BD5

N.C.

98

BL

IF FIRESTAT IS INSTALLED

REMOVE BLUE JUMPER

*

*

Option BD5

Wiring Connections - Firestat,

Option BD5

P/N 256957

P/N 42782

The firestat is shipped separately for field

installation in the return air and/or the supply

air duct. Comply with local building codes.

15

+

~

R

CO2 TRANSMITTER

OUT

(1)

W

G

16

16

+

~

R

OPTION BE15

OUT

(1)

W

96

Option BHB7

Wiring Connections - LON DDC Communication Bus, Option BHB7

G

BMS

CARD

SEE COMMUNICATION CARD INSTALLATION
INSTRUCTIONS FOR DETAILS

LONWORKS CARD INTERFACE CONNECTION

{

SHIELD

A

B

The programmed card is factory-installed in the controller. The wiring is field installed

using 22 gauge, twisted shielded pair wire. Be sure to install the shipped-loose Ferrite

Core around the communication connection.

Lon Card

Ferrite Core

Option GF4

Wiring Connections -

Damper Positioning Control

from Two field provided

Input Switches, Damper

Control Option GF4

15

94

15

95

Field-supplied

Damper Switch 1

Field-supplied

Damper Switch 2

Option BHB8

Wiring Connections - BacNet (MSTP) DDC Communication Bus, Option

BHB8

G

BMS

CARD

SEE COMMUNICATION CARD INSTALLATION

INSTRUCTIONS FOR DETAILS

BACNET MSTP INTERFACE CONNECTION

{

SHIELD

+
-

The programmed card is factory-installed in the controller. The wiring is field installed

using 22 gauge, twisted shielded pair wire. Be sure to install the shipped-loose Ferrite

Core around the communication connection.

BacNet Card

Ferrite Core

7.5 Control Wiring (cont’d)

7.0 Electrical and Wiring (cont'd)

7.5.3 Field Wiring by Control Option (cont’d)