beautypg.com

Reznor YDSA Unit Installation Manual User Manual

Page 13

background image

Form I-Y, P/N 273646R6, Page 13

Installation Instructions for Down Discharge Roof Curbs, Option CJ31 and Option CJ34

1. Refer to FIGURE 6 shown on page 12 and layout the

two curb ends (letter D) and four side pieces (letters B

&C). Verify the side pieces are in the correct positions

(inlet air end vs control end).

2. Attach Curb Corners.

Using the hardware provided, create the corners by

attaching the ends to the side pieces.

16”

(406mm)

1-7/8”(48mm)

4” (102mm)

2 x 6 Wood

Nailer

1-1/2 x 3 lb

Fiberglass

Flashed by the

installer (flashing

must be under

lip of curb)

Lag Screw

and

Washer

Cap

Screws

3. Attach the Splice Plates.

Use the hardware provided to attach splice plates to

join the side rail pieces and create the perimeter of the

curb.

(4) Lag Screws with

washers - top row

(into the nailer)

}

(12) Cap Screws

with washers and nuts

- bottom three rows (cap screw heads

should be on insulation side of rail)

4. Attach the four Cross Supports.

At the holes in curb sides, line up the cross supports

in the orientation illustrated in

FIGURE 6 shown on

page 12. Since the cross supports form the duct con-

nections, be certain that the vertical side of each cross

support is toward the duct opening.
Using two lag screws with washers, at each end of a

cross support, attach the support to the sides. Insert

the screws through the side and into the wood nailer.

Repeat for the other three cross supports.

5. Check the roof curb for squareness.

Adjust the curb so that the diagonal measurements

are equal within a tolerance of ±1/8”(3mm).

6. Level the roof curb.

To ensure a good weatherproof seal between the

cabinet curb cap and the roof curb, the curb must be

leveled in both directions with no twist end to end.

Shim as required and secure the curb to the roof deck

before installing flashing.

7. Install field-supplied flashing.

Roofing

Felts (by others)

Cant Strip

(by installer)

Counter Flashing

(by installer)

MUST be

sealed

between

curb cap and

roof curb.

2 x 6

Wood

Nailer

Insulation

Weld, bolt, or lag screw

curb to deck structure.

Curb

Cap

Cabinet W

all

Roof Curb

}

8. Before placing the unit on the curb:

Apply 1/4” x 1-1/4” foam sealant tape to both the top

surface of the curb rails and the top surface of the

cross supports, being sure to make good butt joints

at all corners. The sealant tape must be applied to

prevent water leakage into the curb area due to blown

rain and capillary action.

Slide the duct work down into the supply (discharge)

and optional return air openings. See dimensions

in

FIGURE 5, page 11. Duct work should have a

minimum 2” (51mm) duct flange.

When it is time to lift the unit onto the curb, comply

with rigging and lifting information in Paragraph 5.4.

IMPORTANT: Verify that the unit will be placed in the

correct airflow orientation to mate properly with the

discharge and return air openings. See

FIGURE 13,

page 19.

FIGURE 7 - Curb Detail and Corner

FIGURE 8 - Attaching Spice Plates

FIGURE 9 -

Installed

Curb