Form I-Y, P/N 273646R6, Page 48

If no adjustment is required, proceed to Step 8.
If an adjustment is required, proceed to Step 7.
Step 7 - High Fire Manifold Pressure Adjustment Heat

Section 2

Remove the cap from the high fire adjustment screw on

the two stage valve. Adjust the pressure setting by turning

the regulator screw IN (clockwise) to increase pressure.

Turn the regulator screw OUT (counterclockwise) to

decrease pressure. Replace the cap. Cycle the burner by

turning the value of the Stg 3 field OFF and ON to actuate

the valve.
Recheck the manifold pressure and repeat Step 7 if

required. If the pressure reading is correct, proceed to

Step 8.
Step 8 - Low Fire Manifold Pressure Reading Heat

Section 2

Set the Value for Stg 3 to OFF. Using the manometer,

measure the pressure on low fire for heat section 2.

Check the pressure with the chart shown below.

Normally adjustments to the factory settings should

not be necessary.
If no adjustment is required, proceed to Step 10.
If an adjustment is required, proceed to Step 9.

Step 9 - Low Fire Manifold Pressure Adjustment Heat

Section 2

Remove the cap from the low fire adjustment screw on the

two stage valve. Adjust the pressure setting by turning the

regulator screw IN (clockwise) to increase pressure. Turn

the regulator screw OUT (counterclockwise) to decrease

pressure. Replace the cap. Cycle the burner by turning

the value of the Stg 2 field OFF and ON to actuate the

valve.
Recheck the manifold pressure and repeat Step 9 if

required. If the pressure reading is correct, proceed to

Step 10.
Step 10 - Close the manual valve. Remove the

manometer. Check for a leak at the pressure taps using a

leak-detecting solution.
If further unit component testing is required proceed with

the instructions in paragraph 10.3 for the remaining test

mode menu screens. If further unit testing is not required,

press the enter key in succession until the cursor is

flashing in the uppermost left hand corner of

screen

E.a.5 and use the up arrow key to navigate to Test Mode

Screen E.a.1. Press the enter key to select the Enable:

field. Press the down arrow key to set the value to OFF.

9.2.2 Checking Gas Pressure (cont’d)

9.2 Gas Heat Section (cont’d)

9.0 Optional Equipment including Heat Sections (cont’d)