Reznor YDSA Unit Installation Manual User Manual

Page 45

background image

Form I-Y, P/N 273646R6, Page 45

Step 4 Modulating Valve Adjustment Instructions (See FIGURE 24B, page 43) - HIGH FIRE SETTING (BUTTON

#1)
1. To enter the high fire setting mode, press and hold button #1 until the LED lights solid red. Release. The valve is

now in the high fire setting mode. Buttons #1 and #2 are used to set desired high fire setting.

2. Press or hold Button #1 to increase gas flow. Each button press equates to the minimum available step size and

will increase flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the

button. Use the feature to rapidly increase the flow.

Press or hold Button #2 to decrease gas flow. Each button press equates to the minimum available step size and

will decrease flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the

button. Use this feature to rapidly decrease the flow.

3. To save the high fire setting, simultaneously hold Buttons #1 and #2 until the LED turns off.

NOTE: Controls left

in any setting mode will default to the current settings and return to normal operating mode after 5 minutes of

inactivity.

4. When the high-fire pressure measurement is correct, proceed to Step 5 to check low fire pressure. If high fire

cannot be accomplished, consult the factory service department.

Step 5 Modulating Valve Adjustment Instructions (See FIGURE 24B, page 43.) - LOW FIRE SETTING (BUTTON

#2)
1. To enter the low fire setting mode, press and hold button #2 until the LED light blinks red. Release. The valve is

now in the low fire setting mode. Buttons #1 and #2 are used to set desired low fire setting.

2. Press or hold Button #2 to decrease gas flow. Each button press equates to the minimum available step size and

will decrease flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the

button. Use this feature to rapidly decrease the flow.

Press or hold Button #1 to increase gas flow. Each button press equates to the minimum available step size and

will increase flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the

button. Use the feature to rapidly increase the flow.

3. To save the low fire setting, simultaneously hold Buttons #1 and #2 until the LED turns off.

NOTE: Controls left

in any setting mode will default to the current settings and return to normal operating mode after 5 minutes of

inactivity.

4. When the low-fire pressure measurement is correct, proceed to Step 6. If low fire setting cannot be

accomplished, consult the factory service department.

Step 5 - Low-Fire Manifold Pressure Reading

From the Test Mode

Screen E.a.5:

Press the enter key until the cursor is flashing on the

Heat Capacity: field.

Adjust the Heat Capacity value to 0% which will result in a signal of 2vdc to the

modulating gas valve.

Using the manometer, measure the manifold pressure on low fire.

Check the pressure

with the chart on page 49. Normally adjustments to the factory settings should

not be necessary.
Follow the procedure in Step 5 to adjust the low fire output pressure of the modulating

valve.

Step 6 - Close the manual valve. Remove the manometer. Check for a leak at the

pressure taps using a leak-detecting solution.
If further unit component testing is required proceed with the instructions in paragraph

10.3 for the remaining test mode menu screens. If further unit testing is not required,

press the enter key in succession until the cursor is flashing in the uppermost left hand

corner of screen E.a.5 and use the up arrow key to navigate to Test Mode

Screen

E.a.1. Press the enter key to select the Enable: field. Press the down arrow key to set

the value to OFF.

Instructions for Measuring Manifold Pressure - Option AG73

(modulation with one heat sections) (cont’d)