beautypg.com

0 mechanical (cont’d), 2 duct connections and duct work – Reznor YDSA Unit Installation Manual User Manual

Page 22

background image

Form I-Y, P/N 273646R6, Page 22

6.2 Duct

Connections

and Duct work

Requirements and Suggestions for Installing Ducts

Duct connections are in the roof curb designed for the unit; see

FIGURE 2 on page 7,

FIGURE 3 on page 8 or FIGURE 4 on page 9 for duct connection sizes. Down flow roof

curbs are designed for installing duct work from the top before setting the unit on the

curb. Horizontal curbs have return air and supply air duct flanges on the side under the

condenser section. See

Figure 5, page 11 or FIGURE 10, page 14 in Paragraph 5.3.

NOTE: All installations require a discharge air temperature sensor. See Paragraph

7.5.3 for placement of the discharge air sensor in the duct work.

• Type of Duct work - The type of duct installation to be

used depends in part on the construction of the roof

(whether wood joist, steel bar joist, steel truss, pre-

cast concrete) and the ceiling (whether hung, flush,

etc.).

• Duct work Material - Rectangular duct should be

constructed of not lighter than No. 26 U.S. gauge

galvanized steel or No. 24 B & S gauge aluminum.

• Duct work Structure - All duct sections 24 inches

(610mm) or wider, and over 48 inches (1219mm) in

length, should be cross broken on top and bottom and

should have standing seams or angle-iron braces.

Joints should be S and drive strip, or locked.

• Through Masonry Walls - No supply air duct should

come in contact with masonry walls. Insulate around

all air ducts through masonry walls with not less than

1/2” (13mm) of insulation. 1” (25mm) is recommended.

• Through Uncooled/Unheated Space - Insulate all

exposed supply air ducts passing through an uncooled

or unheated space with at least 1/2” (13mm) of

insulation. 1” (25mm) is recommended.

• Duct Supports - Suspend all ducts securely from

buildings members. Do not support ducts solely by the

unit duct connections.

• Duct Sizing - Proper sizing of the supply air duct work

is necessary to ensure a satisfactory installation. The

recognized authority for such information is the Air

Conditioning Contractors Association, 2800 Shirlington

Road, Suite 300, Arlington, VA 22206 (www.acca.

org). A manual covering duct sizing in detail may be

purchased directly from them.

• Duct Connections - To minimize sound and vibration

transmission, use flexible duct connections. Ducts

must be attached and sealed to provide airtight

connections.

• Return Air Duct/Grill Size - Make certain that return

air ducting or grill has a free area equal to the return

duct size connection.

CAUTION: An

external duct system

static pressure not

within the limits on

the rating plate may

overload the motor.

The cooling section drain pan is below the coil access door in the cooling section. The

1-1/4” drain connection is through the side of the cabinet.

Follow the instructions below to install a trap in the drain.

Do not reduce the drain

diameter. Pitch the drain line at least 1/2” (13mm) for every 10 feet (3M) of horizontal

run. Drain lines must not interfere with access panels or doors.

An obstruction in the drain or a poorly designed drain can cause the condensate pan to

over flow. Overflow could result in damage to the unit and/or the building.
If the installation or local code requires, run drain into a waste water system.

6.3 Cooling Section

Condensate

Drain

NOTE: For condensate

drain for high-efficiency

gas heat section, see

Paragraph 9.2.

Control Access

Dual Gas Heat

Section

Hot

Air

Cool

Air

FIGURE 15 - When installing a

unit with a dual heat section,

avoid an immediate “T” in the

discharge (supply) duct.

An immediate “T” in the discharge duct

may allow stratification of the air resulting

in hot air only moving down one segment

of the duct.

Avoid this supply duct configuration. If the

configuration is not avoidable, provide air

mixing devices in the duct work.

Installing the Exhaust Hood on a Unit with

Option PE_ Power Exhaust

The exhaust opening is in the door panel.
1) Position the hood side to align with the

holes in the door panel. Attach with

sheetmetal screws.

2) Repeat to attach the other side.

3) Slide the top in place over the side panels.

Attach the top to the door and the side

panels.

FIGURE 14D -

Installing Exhaust

Hood for Power

Exhaust Option

PE__ without a

wheel

6.0 Mechanical (cont’d)

This manual is related to the following products: