BTUH Inputs and Capacities by Altitude in the United States

Altitude

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum Input

(Applies to

AG71)

5:1 Modulation

Minimum Input

(Applies to

AG73)

Feet

Meters

G150

G225

G300

0-2000

0-610

150,000

136,500

75000

30,000

225,000

204,750

112500

45,000

300,000 273,000

150,000

60,000

2001-3000

611-915

138,000

125,580

69000

27,600

207,000

188,370

103500

41,400

276,000 251,160

138,000

55,200

3001-4000

916-1220

132,000

120,120

66000

26,400

198,000

180,180

99000

39,600

264,000 240,240

132,000

52,800

4001-5000

1221-1525

126,000

114,660

63000

25,200

189,000

171,990

94500

37,800

252,000 229,320

126,000

50,400

5001-6000

1526-1830

120,000

109,200

60000

24,000

180,000

163,800

90000

36,000

240,000 218,400

120,000

48,000

6001-7000

1831-2135

114,000

103,740

57000

22,800

171,000

155,610

85500

34,200

228,000 207,480

114,000

45,600

7001-8000

2136-2440

108,000

98,280

54000

21,600

162,000

147,420

81000

32,400

216,000 196,560

108,000

43,200

8001-9000

2441-2745

102,000

92,820

51000

20,400

153,000

139,230

76500

30,600

204,000 185,640

102,000

40,800

BTUH Inputs and Capacities by Altitude in the United States

Altitude

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies

to AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Feet

Meters

G302

G372

G452

0-2000

0-610

300,000

273,000

75,000

30,000

375,000

341,250

112,500

45,000

450,000 409,500

112,500

45,000

2001-3000

611-915

276,000

251,160

69,000

27,600

345,000

313,950

97,500

39,000

414,000 376,740

103,500

41,400

3001-4000

916-1220

264,000

240,240

66,000

26,400

330,000

300,300

90,000

36,000

396,000 360,360

99,000

39,600

4001-5000

1221-1525

252,000

229,320

63,000

25,200

315,000

286,650

82,500

33,000

378,000 343,980

94,500

37,800

5001-6000

1526-1830

240,000

218,400

60,000

24,000

300,000

273,000

75,000

30,000

360,000 327,600

90,000

36,000

6001-7000

1831-2135

228,000

207,480

57,000

22,800

285,000

259,350

67,500

27,000

342,000

311,220

85,500

34,200

7001-8000

2136-2440

216,000

196,560

54,000

21,600

270,000

245,700

60,000

24,000

324,000 294,840

81,000

32,400

8001-9000

2441-2745

204,000

185,640

51,000

20,400

255,000

232,050

52,500

21,000

306,000 278,460

76,500

30,600

Feet

Meters

G525

G602

0-2000

0-610

525,000

477,750

131,250

52,500

600,000

546,000

150,000

60,000

2001-3000

611-915

483,000

439,530

120,750

48,300

552,000

502,320

138,000

55,200

3001-4000

916-1220

462,000

420,420

115,500

46,200

528,000

480,480

132,000

52,800

4001-5000

1221-1525

441,000

401,310

110,250

44,100

504,000

458,640

126,000

50,400

5001-6000

1526-1830

420,000

382,200

105,000

42,000

480,000

436,800

120,000

48,000

6001-7000

1831-2135

399,000

363,090

99,750

39,900

456,000

414,960

114,000

45,600

7001-8000

2136-2440

378,000

343,980

94,500

37,800

432,000

393,120

108,000

43,200

8001-9000

2441-2745

357,000

324,870

89,250

35,700

408,000

371,280

102,000

40,800

BTUH Inputs and Capacities by Altitude in the United States

Altitude

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies

to AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Normal

Input

Thermal

Output

Capacity

4-Stage

Minimum Input

(Applies to

AG72)

10:1 Modula-

tion Minimum

Input (Applies to

AG74)

Feet

Meters

H102

H125

H150

0-2000

0-610

100,000

80,000

25,000

10,000

125,000

100,000

37,500

15,000

150,000 120,000

37,500

15,000

2001-3000

611-915

92,000

73,600

23,000

9,200

115,000

92,000

32,500

13,000

138,000

110,400

34,500

13,800

3001-4000

916-1220

88,000

70,400

22,000

8,800

110,000

88,000

30,000

12,000

132,000 105,600

33,000

13,200

4001-5000

1221-1525

84,000

67,200

21,000

8,400

105,000

84,000

27,500

11,000

126,000 100,800

31,500

12,600

5001-6000

1526-1830

80,000

64,000

20,000

8,000

100,000

80,000

25,000

10,000

120,000

96,000

30,000

12,000

6001-7000

1831-2135

76,000

60,800

19,000

7,600

95,000

76,000

22,500

9,000

114,000

91,200

28,500

11,400

7001-8000

2136-2440

72,000

57,600

18,000

7,200

90,000

72,000

20,000

8,000

108,000

86,400

27,000

10,800

8001-9000

2441-2745

68,000

54,400

17,000

6,800

85,000

68,000

17,500

8,500

102,000

81,600

25,500

10,200

Feet

Meters

H175

H202

H402

0-2000

0-610

175,000

140,000

50,000

20,000

200,000

160,000

50,000

20,000

400,000 320,000

100,000

40,000

2001-3000

611-915

161,000

128,800

43,000

17,200

184,000

147,200

46,000

18,400

368,000 294,400

92,000

36,800

3001-4000

916-1220

154,000

123,200

39,500

15,800

176,000

140,800

44,000

17,600

352,000 281,600

88,000

35,200

4001-5000

1221-1525

147,000

117,600

36,000

14,400

168,000

134,400

42,000

16,800

336,000 268,800

84,000

33,600

5001-6000

1526-1830

140,000

112,000

32,500

13,000

160,000

128,000

40,000

16,000

320,000 256,000

80,000

32,000

6001-7000

1831-2135

133,000

106,400

29,000

11,600

152,000

121,600

38,000

15,200

304,000 243,200

76,000

30,400

7001-8000

2136-2440

126,000

100,800

25,500

10,200

144,000

115,200

36,000

14,400

288,000 230,400

72,000

28,800

8001-9000

2441-2745

119,000

95,200

22,000

8,800

136,000

108,800

34,000

13,600

272,000 217,600

68,000

27,200

Feet

Meters

H502

H602

H702

0-2000

0-610

500,000

400,000

150,000

60,000

600,000

480,000

150,000

60,000

700,000 560,000

175,000

70,000

2001-3000

611-915

460,000

368,000

130,000

52,000

552,000

441,600

138,000

55,200

644,000 515,200

161,000

64,400

3001-4000

916-1220

440,000

352,000

120,000

48,000

528,000

422,400

132,000

52,800

616,000 492,800

154,000

61,600

4001-5000

1221-1525

420,000

336,000

110,000

44,000

504,000

403,200

126,000

50,400

588,000 470,400

147,000

58,800

5001-6000

1526-1830

400,000

320,000

100,000

40,000

480,000

384,000

120,000

48,000

560,000 448,000

140,000

56,000

6001-7000

1831-2135

380,000

304,000

90,000

36,000

456,000

364,800

114,000

45,600

532,000 425,600

133,000

53,200

7001-8000

2136-2440

360,000

288,000

80,000

32,000

432,000

345,600

108,000

43,200

504,000 403,200

126,000

50,400

8001-9000

2441-2745

340,000

272,000

70,000

28,000

408,000

326,400

102,000

40,800

476,000 380,800

119,000

47,600

Feet

Meters

H802

0-2000

0-610

800,000

640,000

200,000

80,000

2001-3000

611-915

736,000

588,800

184,000

73,600

3001-4000

916-1220

704,000

563,200

176,000

70,400

4001-5000

1221-1525

672,000

537,600

168,000

67,200

5001-6000

1526-1830

640,000

512,000

160,000

64,000

6001-7000

1831-2135

608,000

486,400

152,000

60,800

7001-8000

2136-2440

576,000

460,800

144,000

57,600

8001-9000

2441-2745

544,000

435,200

136,000

54,400

9.2 Gas Heat Section (cont’d)