Page 64

background image

Form I-Y, P/N 273646R6, Page 64

17. Saving Maximum Fan Speed Values Adjusted in

Step 10

Press the escape key to return to the service menu

and navigate to the TAB sub menu.

Press the enter key to access the

TAB menu screen

E.b.1

This screen is used to save all adjustable unit

parameters. The Set Max SF Spd? and Set Max EF

Spd? Modifiable fields are used to set the optional

Summer / Winter and High/ /Low fan speed set

points for saving to the maximum fan speed values

determined in Step 10.
Press the enter key to navigate to the

Set SF Max

Spd? Modifiable field and press the up key to set the

value to YES. After a two-second period, the value

will automatically return to the NO state.
If applicable, press the enter key to advance to the

Set Max EF Spd? Modifiable field and press the

10.4 Other Control Settings

1. From the Main Screen, press the

program key to access the main

menu.

Press the up or down arrow keys

to navigate to the

B. Schedule

submenu and press the enter key to

select.


2. From Screen B.1, press the enter

key to access the modifiable date and

time fields and set them to the current

date and time.

3. Once set, press the enter key in

succession until the cursor is blinking

in the uppermost left hand corner of

the screen and press the down arrow

key to advance to

Screen B.2.

From

Screen B.2, press the enter

key to access the modifiable DST

fields and set the values accordingly.

Once set, press the escape key in

succession to return to the main

screen.

10.0 Commissioning and Startup (cont’d)

10.3 Unit Test Mode and Setting Fan CFM (cont’d)

Test Mode Detailed Description (cont’d)

up key to set the value to YES. After a two-second

period, the value will automatically return to the NO

state.
To save unit and fan speed parameters press the

enter key to navigate to the

Save? Modifiable field

and press the up key to set the value to YES. After a

two-second period, the value will automatically return

to the NO state.
Unit parameters have now been successfully saved

to the controller permanent memory. From this point

forward the

most recently saved unit parameters

can be restored using the

Restore? Modifiable field.

The unit test and setting fan speed procedure is now com-

plete. Press The escape key in succession to return to the

main screen.

10.4.1 Set the Date

and Time on the

Controller Clock