* Heat sections with dual furnaces. When only one size is listed, both furnaces are the same size and two identical high pres-

sure switches are used. Dual furnace heat sections with electronic modulation Option AG74 have one low pressure switch

.

A proprietary electronically controlled venter system provides the required volume of

combustion air and correct gas pressure to maintain thermal efficiency during periods

of modulation. Change of venter speed is controlled by an electronic board located in

the heat section.
The venter system always operates at high speed during pre-purge and post-purge

periods. Speed selection occurs after there is a call for burner ignition.

Two-Speed Venter

System

Location of Combustion

Air Inlet Openings and

Vent Outlets

Vent location depends on the type of gas heat section. Refer to

FIGURE 27A, shown

below

or FIGURES 28A & 28B, page 56 for vent outlet locations and installation

requirements that apply.
The combustion air inlet openings are located in the doors on the control end of the

unit. Keep all openings clean and free of obstructions.

Vent Temperature Limit

Switch

All furnaces in the high-efficiency gas heat section are equipped with a temperature

activated, manually reset switch to limit the temperature of the vent gases to below

145°F. The switch is attached to the side of each venter housing (single heat sections

have one; dual heat sections have two). See location in

FIGURE 25, page 52.

If the setpoint is reached, the switch will activate to interrupt the electric supply to the

gas valve. If the vent temperature switch is activated, identify and correct the cause

before resetting the switch. Refer to the Maintenance Section in Form O-Y for informa-

tion on probable causes and instructions on resetting the switch.

Venting a Standard

(non-condensing) Gas

Heat Section

A unit with a standard efficiency

(non-condensing) heat section

has a vent outlet box as shown

in

FIGURE 27A on the left.

If an extension is required, see

Option CC3 or CCD3 below.

Control End of Unit

Optional Gas

Heat Section

Control Access

Condenser

Section

Combustion Air intake

Openings in Doors

(applies to all gas heat

sections)

Single Vent Outlet Box

on a unit with a standard

efficiency (non-

condensing) gas heat

section with either

single or dual furnaces.

FIGURE 27A - Vent

Outlet and Combustion

Air Inlet Locations

Vertical Vent Extension,

Option CC3 or CCD3

- applies to standard

(non-condensing) gas-

fired heat section

If local code requires 4-ft (1.2M) vertical clearance between the flue outlet and the

fresh air intake of the heating system or the building, install a vertical vent with a vent

cap. The option package includes the vent cap. The vent pipe is field supplied. The

vent pipe must be the same diameter as the vent connection.
Remove the cover on the side of the unit to attach the field-supplied vent pipe.

Venting a High-Efficiency (condensing) Gas Heat Section

The high-efficiency heat section vents through a Schedule 40 PVC pipe that extends

from the unit in the locations shown in

FIGURE 28A shown on page 56. The vent must

be terminated with a field-provided 45° elbow of Schedule 40 PVC or CPVC vent pipe.

NOTE: In Canada, all PVC vent pipe must be approved to ULC S636.
Attach the 45° elbow at each vent outlet in the orientation illustrated so that the flue

products are directed downward. (

NOTE: Elbow(s) must be 45°.)

Combustion Air Switches for Above 6000 ft. (1830 m) - (cont’d)

Heat

Section

Option

Heat

Size(s)

(Btuh)

High Pressure Switch

Heat

Section

Option

Heat

Size(s)

(Btuh)

High Pressure Switch

Setpoint

Off

Label

Color

Switch

P/N

Setpoint

Off

Label

Color

Switch

P/N

Negative Pressure (iwc)

Negative Pressure (iwc)

H175*

75,000

1.35

Green

273554

G372* 150,000

1.35

Green

273554

100,000

1.35

Green

273554

225,000

1.35

Green

273554

H200

200,000

1.35

Green

273554

G452* 225,000

1.35

Green

273554

H202*

100,000

1.35

Green

273554

G452* 225,000

1.35

Green

273554

H300

300,000

1.45

Orange

273555

G525

225,000

1.35

Green

273554

H400

400,000

1.45

Green

273555

300,000

1.25

Blue

273553

H402*

200,000

1.35

Green

273554

G602

300,000

1.25

Blue

273553

H502*

200,000

1.35

Green

273554

300,000

1.45

Orange

273555