14. Electric Heat Only - From Test Mode Screen E.a.5,

press the enter key until the cursor is flashing on the

Heat Capacity: field. Press the up arrow key to set

the Heat Capacity value to 100% and press the enter

key until the cursor is flashing on the

Stg 1: field.

Press the up arrow to set the Stg 1 value to ON.

Using a digital volt meter, check for the appropriate

line voltage on the load side of the Stg 1 contactor to

verify that it has energized. Once verified, press the

down arrow key to set the Stg 1 value back to OFF.


If no voltage is present, refer to Form O-Y for

instructions.

Depending upon configuration the unit may be

equipped with up to 6 stages of electric heating.

Perform the same procedure for the remaining

applicable heating stages.

NOTE: The heat capacity: field is only associated

with Stg 1.

15. Gas Heat Only - If the unit is equipped with gas

control system Option AG73 or AG74, the modulating

gas valve and its associated heat capacity value will

need to be used to verify and (if required) adjust the

manifold pressure settings. See paragraph 9.2 for

checking gas pressure.

To test staged flame proving, see the following

instructions.


From the Test Mode

Screen E.a.5, press the enter

key until the cursor is flashing on the Heat Capacity

Field:

Option AG73 or AG74 only - Press the up arrow

key to set the Heat Capacity value to 30%.

Press the enter key until the cursor is flashing on

the

Stg 1: field.

Press the up arrow to set the Stg 1 value to ON.

NOTE: Depending on the gas control option (Option

AG71, AG72. AG73, or AG74), the unit may be

equipped with up to 4 stages of gas heating turned

on via the controller menu. If applicable, perform the

following step for stage 2.

Press the enter key until the cursor is flashing on

the

Stg 2: field.

Press the up arrow to set the Stg 2 value to ON.

If no voltage is present at the contactor(s), refer to

Form O-Y for instructions.

Press the enter key in succession until the cursor

is flashing in the uppermost left hand corner of the

screen and use the up arrow key to navigate to Test

Mode

Screen E.a.1. Press the enter key to select the

Enable: field. Press the down arrow key to set the

value to OFF.

Press the enter key in succession until the cursor

is flashing in the uppermost left hand corner of the

screen and use the down arrow key to advance to

the Test Mode

Screen E.a.11.

If the gas heating section(s) have proved flame, the

associated DI15 (and DI16 if applicable) will show

status ON.
NOTE: Allow a 3-minute period for flame proving.
Once verified, press the down arrow key to set the

Stg 1 and Stg 2 values back to OFF.
If the DI15 (and DI16) fail to show status ON, refer to

Form O-Y for instructions.


Press the enter key in succession until the cursor

is flashing in the uppermost left hand corner of the

screen and use the up arrow key to navigate to the

Test Mode

Screen E.a.6.

16. Optional Energy Recovery with or without

Optional Preheat - From Test Mode Screen E.a.6,

press the enter key until the cursor is flashing on the

Wheel: field.

Press the up arrow key to set the wheel value to

ON. Press the enter key to select the

Preheat: field.

Press the up arrow to set the preheat value to ON.

Using a digital volt meter, check for the appropriate

line voltage on the load side of the wheel contactor

and preheat contactor (if applicable) to verify that

they have energized. Once verified, set the values for

the

Wheel: field and the Preheat: field to OFF.