beautypg.com

0 electrical and wiring, 1 general, 2 supply wiring – Reznor YDSA Unit Installation Manual User Manual

Page 23

background image

Form I-Y, P/N 273646R6, Page 23

All electrical wiring and connections including electrical grounding MUST be made in

accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition). In addi-

tion, the installer should be aware of any local ordinances or electric company require-

ments that might apply.

7.1 General

Check the rating plate for the supply voltage and current requirements. Run a separate

line voltage supply directly from the main electrical panel, making connection at the

disconnect switch. See

FIGURE 2 on page 7, FIGURE 3 on page 8 or FIGURE 4 on

page 9 for location of supply wiring entrance.
If the system has dual disconnect switches (Option BA7), two supply wires are required

(See

FIGURE 17A, page 24 and FIGURE 17B, page 24).

7.2 Supply Wiring

7.0 Electrical and

Wiring

7.2.1 Disconnect

Switch

The system must have a remote disconnect switch, a built-in disconnect switch, or

both.
If ordered with a built-in disconnect switch, the system will be factory equipped with

one or two built-in non-fusible, lockable disconnect switch(es). The built-in disconnect

switch(es) (Option BA6 or BA7) require copper wiring with amp capacity based on

75°C maximum temperature rating at the line side terminals.
If the system does not have a built-in disconnect switch, a field-provided or optional

shipped-separate, wall-mounted disconnect switch is required. It is recommended

that there is at least four feet (1.2M) of service room between the switch and system

access panels. All external wiring must be within approved conduit and have a mini-

mum temperature rise rating of 60°C.

Run conduit so that it does not interfere with

the system access panels. When providing or replacing fuses in a fusible disconnect,

use dual element time delay fuses and size according to the rating plate.

WARNING

To prevent injury or death due to electrocution or contact

with moving parts, lock an open disconnect switch.

WARNING

If the unit includes a gas furnace, always turn off the gas

when you turn off the power supply.

The design of the drain trap is important. Since the condensate drain pan is on the

blower inlet side, there is a negative pressure at the drain relative to the ambient. The

trap height must account for this static pressure difference. Maximum negative static

can be determined by reading the negative pressure at the blower inlet and adding .2”

iwc to allow for dirty filters.
If dimension "B" in

FIGURE 16A shown below is not tall enough, the water seal will not

hold, and air will be drawn through the drain pipe into the unit. If the outlet leg of the

trap is too tall, water will back up into the drain pan. As condensate forms during normal

operation, the water level in the trap rises until there is a constant outflow.

FIGURE 16A

shown below illustrates the appropriate dimensions for trapping a negative pressure

system.

Condensate Drain Trap in Cooling Coil Drain

To prevent air

from entering

always close

the cleanout.

Water Flow

Unit

FIGURE 16B -

Drain Trap with

Clean out

B

A

A/2

C

L

C

L

C

L

Unit

Water Flow

Water Flow

A = 1" (25mm) for each 1"

(25mm) of maximum

static pressure plus 1"

(25mm)

B = A + A/2

FIGURE 16A - Condensate

Drain Trap Dimensions

6.3 Cooling Section

Condensate

Drain (cont’d)

This manual is related to the following products: