beautypg.com

Reznor YDSA Unit Installation Manual User Manual

Page 53

background image

Form I-Y, P/N 273646R6, Page 53

DSI Control Module

LED Flash Codes

Flash Code Description

Fast Flash Normal operation

Steady OFF No power, blown fuse, or defective board

1

Low pressure switch stuck open

2

Low pressure switch stuck closed

3

High pressure switch stuck open

4

High pressure switch stuck closed

5

Limit switch open

6

Ignition lockout (failed ignition)

7

Too many (5) limit switch losses

8

Too many (5) flame losses

9

Too many (3) high pressure switch losses during one call for heat

All gas furnaces are equipped with a temperature activated auto reset limit control.

Depending on size, the control is factory set at either 200°F or 250°F and is non-

adjustable. If the setpoint is reached, the limit control will interrupt the electric supply

to the gas valve. This safety device provides protection in the case of a lack of airflow

due to dirty filters or a restriction at the inlet or outlet.
The limit control switch is mounted on the side of the heat exchanger (See location in

FIGURE 23, page 39 or FIGURE 24A, page 43).

High Temperature

Limit Control

FIGURE 26 - DSI

Control Module

LED Light

Combustion Air and

Venting

Combustion Air Proving Switch

The combustion air proving switch is a pressure sensitive switch that monitors air pres-

sure to ensure that proper combustion air is available. The switch is single pole/single

throw with the normally open contacts closing when the proper airflow is sensed in the

system.

The gas heat section is power vented. Presence of combustion air pressure is moni-

tored by a combustion air proving switch located in the heat section.

On start-up when the heater is cold, the sensing pressure is at the most negative

level, and as the heater and flue system warm up, the sensing pressure becomes less

negative. After the system has reached equilibrium (about 20 minutes), the sensing

pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pressure to be out-

side the switch setpoint, the pressure switch will function to shut off the main burners.

The main burners will remain off until the system has cooled and/or the flue system

resistance is reduced. The table below lists the approximate water column negative

pressure readings and switch set points for sea level operating conditions.

CAUTION: The auto reset limit control will continue to shut down the heat section until the

cause is corrected. Never bypass the limit control; hazardous conditions could result.

This manual is related to the following products: