Form I-Y, P/N 273646R6, Page 11

5.3.1 Down flow Roof

Curbs

Both Option CJ31 and CJ34 are 16" (406mm) high roof curbs designed for vertical

(down) discharge. These curbs include integral cross supports for supply air and

optional return air duct work.

FIGURE 5 - Layout, Dimensions, and Weights of Option CJ31 & CJ34 Roof Curbs

Suppl

y

Air

Return

Air

Downflow Curb Options CJ31 and

CJ34

2x6

Wood

Nailer

Insulation

16”

(406mm)

Cross-Section

View

(Control End

of Unit)

(Inlet Hood End)

(Condenser Side of Unit - Base extends

30” / 761mm beyond this side of c

urb.)

Return

Air

(DxF)

Supply

Air

(DxE)

Unit

Airflow

A

B

D

E

F

Top View

C

G

H

Curb

Layout

Option

Model and Size

Cabinet

Size

A

B

C

D

E**

F**

G

H

(Outside of Curb Rails) (Area Inside the Curb*)

CJ31

No Energy

Wheel

YDHA & YDMA 060,

090, 120, 150

1

119-11/16

(3040)

43-7/16

(1103)

115-15/16

(2945)

39-11/16

(1008)

31

(787)

17

(432)

25-3/4

(654)

14-29/32

(379)

YDHA & YDMA 180,

210, 240 YDSA 120, 150

2

123-11/16

(3141)

50-11/16

(1287)

119-15/16

(3046)

46-15/16

(1192)

31

(787)

19

(483)

25-13/16

(656)

18-13/16

(478)

YDHA & YDMA, 300,

360 YDSA 180, 210

3

154-11/16

(3929)

63-11/16

(1618)

150-15/16

(3834)

59-15/16

(1522)

31

(787)

21

(483)

28-7/32

(717)

28

(711)

CJ34

With Energy

Wheel

YDHA & YDMA 060,

090, 120, 150

1

128

(3251)

43-7/16

(1103)

124-1/4

(3156)

39-11/16

(1008)

31

(787)

17

(432)

25-3/4

(654)

23-1/4

(591)

YDHA & YDMA180, 210,

240 YDSA 120, 150

2

132

(3353)

50-11/16

(1287)

128-1/4

(3257)

46-15/16

(1192)

31

(787)

19

(483)

25-13/16

(656)

27-1/8

(689)

YDHA & YDMA, 300,

360 YDSA 180, 210

3

154-11/16

(3929)

63-11/16

(1618)

150-15/16

(3834)

59-15/16

(1522)

31

(787)

21

(483)

28-7/32

(717)

28

(711)

Weights of Downflow Roof

Curb Option CJ31 and CJ34

by Cabinet Size

Roof

Curb

Cabinet 1

Cabinet 2

Cabinet 3

lbs

kg

lbs

kg

lbs

kg

Option

CJ31

237

108

257

117

322

146

Option

CJ34

248

112

268

122

322

146

* Area enclosed by the roof curb must comply with clearance to

combustible materials. If the roof is constructed of combustible

materials, area within the roof curb must be ventilated, left open,

or covered with non-combustible material which has an “R” value

of at least 5. If area within curb is left open, higher radiated sound

levels may result.

NOTE: If installing a unit with a high efficiency,

condensing gas-fired heat section, the area within the curb must be

left open.

** When cutting only duct openings, cut “E” & “F” dimensions 1/4”

(6.4mm) in from duct opening to allow clearance. Cut the curb rail

sides of the duct opening(s) parallel to the curb rail. For Cabinet

Size 1, measure a maximum of 1-1/2” (38mm) in from the side rail.

For Cabinet Size 2, measure a maximum of 3/4” (19mm) in from

the side rail.

*** See chart on page 68 for cross-reference by Model Size or

Model and Heat Size to Cabinet Size.

Dimensions - inches (mm)