beautypg.com

3 electric heat section – Reznor YDSA Unit Installation Manual User Manual

Page 58

background image

Form I-Y, P/N 273646R6, Page 58

FIGURE 29B - Condensate Drain Trap

for High-Efficiency Heat Section Drain

Trap Installation:
Install the trap as shown in either illustration.

The trap must be installed vertically with the

float above the spring as shown. DO NOT

INSTALL THE TRAP HORIZONTALLY.
(

NOTE: Check kit contents; some

connections shown and all straight PVC

parts are field supplied.)
Trap Maintenance:
Open the cleaning ports and use the brush

provided to clean the drain.
To clean the trap and float, unscrew the

retaining ring and remove the bottom section

of the trap. Remove float and spring. Clean

all parts with soapy water.
Re-assemble by inserting the spring and

float into the bottom trap section, position the

bottom section into the top, and secure with

the retaining ring.

Sample Configurations -- Trap may be installed in a

variety of configurations but MUST be vertical.

Trap

Trap

Trap

Trap

High Efficiency Heat Section Condensate Drain (cont’d)

Instructions for Installing High Efficiency Heat Section Condensate

Drain

1) Attach the field-provided 1/2” PVC pipe to the condensate drain connection(s) as

shown in

FIGURE 29A, page 57. If the units has dual heat sections, connect a

PVC pipe to each drain. If there are two drains, join the drains with a field-provided

tee before installing the trap.

2) Install the freeze resistant trap, P/N 271064 (FIGURE 29A, page 57). Refer to

FIGURE 29B, shown below and follow the manufacturer’s instructions to install

and maintain the trap.

3) Continue the line from the trap inside the building and into a sanitary drain.

9.3 Electric Heat

Section

A unit with an electric heat section is equipped to provide from 30 to 120 kw of electric

heat. The electric elements are located in the discharge airstream and are accessible

through the electrical compartment.
An electric heat section in a Model YDSA may have either two to four stage control or

SCR modulating control. Models YDHA and YDMA are equipped with SCR modulating

control. Call for heat and staging are controlled by the unit controller.

Modulating heating operation is controlled by an SCR modulating control. There will be

one or two SCR controllers located on an electrical panel in the electric heat section.

WARNING

The heatsink on the SCR power controller is hot to the touch.

SCR Controller

DANGER

High voltages are present on the terminals of the SCR power

controller(s).

Modulating Electric Heat

9.2 Gas Heat Section (cont’d)

9.0 Optional Equipment including Heat Sections (cont’d)

This manual is related to the following products: