FIGURE 17A - Disconnect Switch Wiring Connections

Field-supplied or

Option CP

Disconnect Switch

Field-supplied or Option CP

Disconnect Switch (No BA Option)

Supply V

oltage

(See MCA

on rating plate to

determine wire size.)

Supply V

oltage

(See MCA

on rating plate to

determine wire size.)

Supply V

oltage

(See MCA

on rating plate to

determine wire size.)

Field wiring

Factory wiring

GRD

G

Option BA6 Lockable Disconnect Switch

or Circuit 1 of Option BA7 Dual Lockable Disconnects

Green

Green

Field-supplied or

Option CP

Disconnect Switch

Circuit 2 of Option BA7 Dual Lockable Disconnects

GRD

L3

T3

T1

L1

Black

L1

L3

L2

T2

L2

GRD

L3

T3

T1

L1

L2

T2

G

H

J

DUAL POWER

CIRCUITS

(Option BA7)

CIRCUIT 1 is for DX equipment (compressors, condenser fans,

optional phase/loss monitor, and associated contactors).

CIRCUIT 2 is for the blower, all dampers, optional heating section, optional

power exhust or energy recovery wheel, and other non-DX components.

L1

L2

L3

Yellow

Red

Black

Yellow

Red

Option BA6

Disconnect

Switch

Opening

for Power

Supply

Option BA7

Disconnect

Switches

Openings

for Power

Supplies

Circuit 1

Circuit 2

FIGURE 17B - Built-

in Disconnect Switch

Options BA6 and BA7

7.2.2 Supply Voltage

The electric supply to the unit must meet stringent requirements for the system to oper-

ate properly. Voltage supply should be within ±10% or as stated on the rating plate.
Maximum imbalance on a 3-phase system is 2%.
If the power supply is not within these tolerances, contact the power company prior to

operating the system.

CAUTION: If this unit is allowed to operate on an electric supply that is

not within the specified tolerances, the product warranty shall be void.

Follow instructions below to check.
Check Voltage Supply - See voltage use range on the rating plate. Measure (and

record) each supply leg voltage at all line disconnect switches. Readings must fall

within the allowable range.
Check Voltage Imbalance - In a 3-phase system, excessive voltage imbalance

between phases will cause compressor motors to overheat and eventually fail. Maxi-

mum allowable imbalance is 2%. To determine voltage imbalance, use recorded volt-

age measurements taken above in the following formula.

Key:

V1, V2, V3 = line voltages as measured

VA (average) =

(V1 + V2 + V3)

3

VD = line voltage (V1, V2, or V3) that deviates farthest from average (VA)

Formula:

% Line Voltage Imbalance =

[100 x (VA - VD)]

VA

7.2 Supply Wiring (cont’d)