Potter PFC-6030 User Manual
Page 84
5-78
PFC-6030 • 5403595 • Rev C • 2/13
To configure points:
Click on the
1.
Points function to display the "Points Configuration" window.
Example of a Configuration Window
Figure 103.
Note: Click the columns to sort devices by the field selected, i.e., "Name", "Alarm Verification" or "Low Temp Trouble".
Supervisory
•
– Designates a detector as a supervisory input instead of an alarm input.
Alarm
•
Verification – Specifies that a detector will utilize the alarm verification feature.
Low Temp Trouble
•
– Indicates that a device is below 40̊F.
Devices are listed by “
2.
Built-in SLC” device addresses, followed by the NACs and I/O circuits.
Note: Click on the “Device” field to sort the list by PWR Supply followed by SLCs.
To configure a single point:
Double-click in “
1.
Name” field to enter a descriptive name. The current name is highlighted as shown:
enter a new name (up to 16 alphanumeric characters).
2.
Click on drop-down arrow in the
3.
“Function” field. Select a function type from the list.
Example of Configuring a “Single” Point
Figure 104.
Continue configuring other points, as needed.
4.