beautypg.com

I1 i2 i 3 i 4 – Potter PFC-6030 User Manual

Page 35

background image

3-29

PFC-6030 • 5403595 • Rev C • 2/13

The 50 programmable LED outputs are located on connectors P1-P5, each containing ten (10) LeD outputs and two (2) 5vDC

outputs. The system LEDs and PZT control outputs are located on connector P6. LeDs are wired as shown below; no external
resistor is required. All outputs are power limited.

DRV-50 "P1-P5" and "P6" Connectors

Figure 34.

The 4 programmable dry-contact inputs are located on connector P7. All input circuits are power limited and use a 5.1k eOL

resistor. The inputs can be programmed for any of the contact input functions available for other input circuits available on the

panel.

DRV-50 "P7" Dry-Contact inputs

Figure 35.

The higher current required for the LeD outputs can be provided by the panel, or from an auxiliary power source as shown below.

The auxiliary power can be any 24vDC source, and is fully supervised.

Examples of Wiring DRV-50 from Control Panel or Auxiliary Power Supply

Figure 36.

TRB

SUP

ALR

SIL

EARTH

PWR

PZT-

LED+

LED1

LED10

LED+

LED+

Programmable LED

Connectors P1-P5

System LED and PZT

Connector P6

DWG #608-8

LED PWR P -Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

control panel

LED PWR P -Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

aux supply

Power from

auxiliary

supply

DWG #608-9B

Dry Contact Inputs (P7)

I1

I2

I

3

I

4

5.1k

5.1k

5.1k

5.1k

P7

DWG #608-9

Max. wiring resistance = 100 ohm
Max. wiring capacitance = 1 uF
Max. wiring length = 10,000 ft.
Max. IDC voltage = 24 vDC
Max. IDC current = 5 mA